2010-008
.
~
-
TOWN OF QUEENSBURY
742 Bay Road, Queens bury, NY 12804-5902 (518) 761-8201
Community Development - Building & Codes (518) 761-8256
BUILDING PERMIT
Permit Number:
P20100008
Application Number.
A20100008
Tax Map No:
523400-308-016-0002-002-003-0000
Permission is hereby granted to: HUDSON HEADWATERS HEALTH NETWORK
For property located at: 9 CAREY Rd
in the Town of Queensbury, to construct or place
at the above location in accordance with application together with plot plans and other information hereto filed
and approved and in compliance with the NYS Uniform Building Codes and the Queensbury Zoning
Ordinance. Type of Construction Value
Owner Address:
HUDSON HEADWATERS HEALT
1 BROAD ST. PLAZA
GLENS FALLS, NY 12804-0000
Commercial Alteration
Total Value
$140,000.00
$140,000.00
Contractor or Builder's Name / Address
Electrical Inspection Agency
Plans & Specifications
2010-008
3760 sq ft commercial alteration
$451.20 PERMIT FEE PAID - THIS PERMIT EXPIRES:
Wednesday, January 12, 2011
(If a longer period is required, an application for an extension must be made to the code Enforcement Officer
of the Town of Queensbwy before the expiration date.)
Dared at the (O~;:::fit' !l~' January 12,2010
SIGNED BY ~ ",1.'. V '1\ /.,..,.~~ for the Town of Queensbury.
Director of Building & Code Enforcement
~2ji~ ~'l(;-2'~' ~3' -. oFFicE i.iSE ONLy.... - -.... -. --...... -.... - - :
: TAXMAPNO II> :1-" PERMITNO 2010-0CfJ .:
: FEES: PERMIT J{')J - RECREATION /)<J ENGINEERING 1
;!_,
r~.,------~---'-'---4
.
......"................-----------.---.----------................-.-
f...... ... .. _ ..
.
,
,
.
.
.
.
.
,"_._ t~._ ".'~ '.. -r,
-I; -i')-- tiiiU
i"...
PRINCIPAL STRUCTURE: ,
APPLICATION FOR ZONING APPROVAL & BUILDING, PERMIT
A PERMIT MUST BE OBTAINED BEFORE BEGINNING CONSTRUCTION. APPLICATION IS SUBJECT TO
REVIEW BEFORE ISSUANCE OF A VALID PERMIT FOR CONSTRUCTION.
APPLlCANTIBUILDER: T:~.c, L.L. C. OWNER:"U~'ON He.~~vI~,.a<:>
ADDRESS:\SS'l. 2t. ~J~'Qrrf~Vf"Prl) ADDRESS:~ c.f\~'t ~V"t)
PHONE NOS, 51 B.143.Cf3UO PHONE NOS. 1 Col. 0'100
CONTACT PERSON FOR BUILDING & CODES COMPLlANCE1\rft )o\c.LGaf~\(.( PHONE:flt.t1.9~ ~
LOCATION OF PROPERTY: 9 C At.e1 RoM> G.VEE~~aV~\( \J,\{
SUBDIVISION NAME: ~\ll\lf.
PLEASE INDICATE MEASUREMENTS AS REQUIRED BELOW:
CHECK ALL THAT z
APPLY TO YOUR 0 a: d d Of-
Z ~ a: W"-",
PROJECT 0 O. 0 '" '" '" -w
O' a: ~j:~
j::: a: Of- -If- -I
~ is W -1"- ,,-"- W ~
f- "- . ~Ng I oS2z
W 0 -I ~ 0 bt O~ OCW-
z <( <( ~'" f-"- o-Io<l
SINGLE FAMILY
lWO-FAMIL Y
MUL TI-F AMIL Y
(NO.->
TOWNHOUSE "'7 "7/ ./'J S,W
)( ,,;'.., - .e: ... ~
BUSINESS OFFICE 'r?j7 ... ..
,. -,}vv
RETAIL- ..
MERCANTILE
FACTORY OR
INDUSTRIAL
ATTACHED
GARAGE(1. 2, 3)
OTHER
IF COMMERCIAL OR INDUSTRIAL - NAME OF BUSINESS:UV~~o~ "~t\t)W ~~
ESTIMATED CONSTRUCTION COsr:l.Yo} '0'00 FUEL TYPE: G^s
HEAT TYPE? G~s .HOW MANY FIREPLACE(S) "NIt-. AND I OR WOODSTOVES(S):~
ZONING CATEGORY: ARE THERE WETLANDS ON THIS SITE? .YO
IS THIS A HISTORIC SITE? ~"
PROPOSED USE OF BUILDING OR ADDITION: OFf,c:.&s
? 1110 f.. I ~ fir, F .
115// 7-0
Town of Queensbury' Community Development Office' 742 Bay Road, Queensbury, ^
ARE THERE STRUCTURES NOT SHOWN ON PLOT PLAN? ~O
ARE THERE EASEMENTS ON PROPERTY?
~o
'Please complete a separate Application for "Fuel Buming Appliances & Chimneys" available in our office
-_.......-_._-~._--_.-- ---_.-.. .............. .......-....-........................ .....---.. ............. -............ ............. .......................... .............. .................---.... ............. ............. ....-
I acknowledge no construction activities shall be commenced prior to issuance of a valid permit.
I certify that the application, plans, and supporting materials are a true and complete statement I
description of the work proposed, that all work will be performed in accordance with the NY
State Builidng Codes, local building laws and ordinances, and in conformance with local zoning
regulations. I acknowledge that prior to occupying the facilities proposed, I or my agents will
obtain a certificate of occupancy. I also understand that II we are required to provide an as-
built survey by a licensed land surveyor of all newly constructed facilities prior to issuance of a
certificate of occupancy.
Signe
and agree to the ~ve.
~ III
-t:M. & L.1..C
----------------------------------------------------.------------------------------------------------------------------
Director of Buildino & Codes: 761-8256 (for questions
regarding Building Permits. construction codes or septic
systems)
Zonino Administrator: 761-8218 (for questions regarding
required permits. the permit process, application requirements or to
schedule an appointment)
DATE
r~I#~I~I;I',II-,II---'-'-'--"""---""";
: This application / proposed action described herein is :
: found to be in accordance with the zoning Laws of :
: the Town of Queensbury :
, ,
, ,
, ,
, ,
, ,
, ,
, ,
, ,
, ,
, ,
: ZONING APPROVAL :
. ,
, ,
, ,
, ,
: DATE :
. ,
,-,---"",_,__"'I""'---""-"--"'--"'~
"._""""".""-""",,,;;;;;;;--------
.
: Permission is hereby granted to the above
: Applicant to erect or alter the building described
: herein in accordance with said Application:
.
.
,
.
,
.
,
,
,
.
.
,
,
.
,
,
,
.
.
,
.
.
.
,
.
,
.
,
,
,
,
,
.
.
.
-------,----------------------------------;-
BUILDING & CODES APPROVAL
Office Use Onlv
Operating Permit Issued:
Occupancy Type:
Construction Classification:
Assembly Occupancy limit:
Special Conditions:
Yes
No
Revised 9/22/09
Town of Queensbury . Community Development Office' 742 Bay Road, Queensbury, NY 12804
J8ta
I~-
-
-
FIRE MARSHAL'S OFFICE
Town of Queensbunj
742 Bay Road, Queensbury, NY 12804
"Home of Natural Beauty... A Good Place to Live"
PLAN REVIEW
Hudson Headwaters
2010-08
1/14/2010
I have reviewed the submitted drawings for the above project, and offer the
following comments.
1) Provide sprinkler plans prior to installation inc. hydraulic calculations.
2) Truss ID sign age will be required.
3) Provide fire alarm plans prior to installation
4) Fire extinguisher locations to be discussed.
5) Exit signs- change directional arrow as discussed in center aisle.
6) All provisions of Fire Code ofNYS Chapter 14 & Building Code ofNYS
Chapter 33 shall be adhered to during construction.
arshal
Gary K. Stillman
742 Bay Road
Queensbury NY 12804
518761 8205
garys@queensbury.net
Fire Marshal's Office. Phone: 518-761-8206 . Fax: 518-745-4437
firemarshal@queensbunl.net. www.queensbunl.net
(lafeV' is heifer) /-.3 fT,d~
Commercial Final Inspection Redfort"
Office No.: (518) 761-8256
Queensbury Building & Code Enforcement
742 Bay Road, Queensbury, NY 12804
NAME: ~vr~ t~~t!0
LOCATION: ;
ved:
- Depart:7;"'C[)J.~
/o._()o~
. :7-rll-/o
, ,
COMMENTS:
y N NA
Chimney / "B" Vent / Direct Vent Location
Plumbing Vent Through Roof 6" / Roof Complete
Exterior Finish / Grade Complete 6" in 10' or Equivalent
Interior / Exterior Guardrails 42 in. Platform / Decks
Interior / Exterior Ballisters 4 in. Spacing Platform / Decks --
/
Stair Handrail 34 in. - 38 in. / Step Risers 7" / Treads 11" /
Vestibules For Exit doors> 3000 sq. ft. /
All Doors 36 in. w/Lever Handles / Panic Hardware, if required V
Exits At Grade Or Platform 36 (w) x 44" O)/Canopv or EQuiv.
Gas Valve Shut-off Exposed & Regulator (18") Above Grade
Floor Bathroom Watertight / Other Floors Okay
Relief Valve, Heat Trap I Water Temp. 110 Degrees Maximum
Boiler / Furnace Enclosure 1 hr. or Fire Extinguishing System
Fresh Air Supply for Occupancy / Ventilation Combustion
Low Water Shut Off For Boilers
Gas Furnace Shut Off Within 30 ft. or Within Line Of Site
Oil Furnace Shut Off at Entrance to Furnace Area
Stockroom/StoragelReceivinglShipping Room (2 hr.), 1 Y2 doors
> 10% > 1000 sq. ft.
% Hour Corridor Doors & Closers
Firewalls / Fire Separation, 2 Hour, 3 Hour Complete / Fire
Dampers / Fire Doors
Ceiling Fire Stopping, 3,000 sq. ft. Wood Frame
Attic Access 30" x 20" x 30" (h), Crawl Space Access 18" x 24"
Smoke Vents Or Fan, if required
Elevator Operation and Signage / Shaft Sealed
Handicapped Bathroom Grab Bars / Sinks / Toilets
Handicapped Bath / ParkinS! Lot Si2oaS!e
Public Toilet Room Handicapped Accessible
Handicapped Service Counters, 34 in., Checkout 36"
Handicapped Ramp I Handrails Continuous/12 in. Beyond [Both sides) ~
Active Listening System and Signage Assembly Space / /)
Final Electrical ..... Vv ~
'./
Site Plan / Variance required (. ( ~ ~;
Final Survey, New Structure / Flood Plain certification, if reQ.
As-built Septic System Layout Required or On File )
Building Number or Tenant Address on Building or Driveway /
Water Fountain or Cooler V
Building Access All Sides by 20' / Driveable Surface 20' wide J
Okay To Issue Temp. or Permanent C/O V
Okay To Issue C/C
~"-
~,O~
~' ~ ,~~
~~~
>-./4>. ~v &-
~~
~
L:\Building & Codes Forms\Building & Codes\InspectlOn Forms\Commerclal FIllal InspectIon Report.doc
2 : tJ CJ L)~J...e T~
Inspection for Permit to Occu(s'y
permitNo.2%- GOy
Scheduled Inspection Date: 2 -:;--)0 Time:
~~~~~~n~ame: tj~~.;fW~ ~
Fire Marshal's Office
Town of Queensbury
742 Bay Road
Queensbury, NY 12804
Request Rec'd
Phone: (518)761-8206
Fax: (518) 745-4437
Type of InsDedlon N/A Yes No
EXITS:
Exit Access o.l
Exit Enclosure t\V
Exit Discharae l..v
AISLES:
Main Aisle Width nl{
Secondary Aisle Width oJ-
EXIT SIGNAGE
Siqn - normal C1L
Sign - battery UK-
EV AC siqns in rooms -
TRUSS ID SIGNAGE rr:v
EMERGENCY LIGHTING 1?7r.-
FIRE EXTINGUISHER:
Hunq nl
Inspection of extinquisher rY
-
FIRE ALARM SYSTEM I"'. -
Fan Shutdown r:
Fire Sprinkler System (FOCI I!.
Fire Suooression - kitchen -
Fire Suooression - Gas Islan -
Generator -
Hood Installation -
Elevator -
Interior Finishes DL
Storaae -
Compressed Gas ........
Clearance to Sprinklers t
Clearance to Electrical ,
Electric Wirinq Enclosed /Labeled
Combustible Waste I- ..,
Vehicle Imoact Protection -
Knox Box
F.D. Sianaae - Utilitv Rooms r
No Smokina Sians t
Maximum Occupancy Siqn t: L
Emerqency Evacuation Plan C 'J..
X Approved (If no other approvals apply, the B & C Offi~
Cl Denied / call for Recheck
Inspected By:
L:\FireMarshal\FM Forms Masters\permitto occupyform.doc
---
COMMENTS
."-' '" --;"'~~";;S""~,~';.~.- ...... .~...~l
\ Fr~Shi~"('7'rF I
I .o"
1 '. ..,/" 'I'
I ~&"L.;. . II'; .
I'. ".' ..J.\ " .
. I. ~ _--
I _._._...i~. ~~.._.~
L.... _..._ T~~~~i..__.___.._i
e Certificate of Occupancy)
I ~ 3 /YLo r--d o--y.
Rough Plumbing Ilnsu~ation Inspection Report
Office No. (518) 761-8256
Queensbury Building & Code Enforcement
742 Bay Road, Queensbury, NY 12804
NAME:
LOCATION:
a .. Y:l~a~
PE MIT #:
INSPECT ON:
~~-/O
TYPE OF STRUCTURE:
Rou h Plumbin I Nail Plates
Plumb in Vent I Vents in Place
1 % inch minimum Drain Size
Washin Machine Drain 2 inch minimum
Cleanout eve 100 feet I chan e of direction
Pressure Test
Drain I Vent
Air I Head
5 P.S.I. or 10 ft. above hi hest connection for 15 minutes
Pressure Test
Water Supply Piping
Air I Head
50 P .S.I for 15 minutes
Insulation I ~esidential Check I Commercial Check
T ek or Similar Exterior Sealant
Pro r Vent, Attic Vent
Door I Window Sealed No Insulation
Duct I Hot Water Piping Insulation
If uired unheated aces
om . n Air Su for Furnace
ct rk led ro ert I No duct ta
Y N N/A
COMMENTS:
o~\O ~?\'Lf
Rough Plumbing Insulation Reportrevised Nov 172003, revised February 15, 2005, revised January 7, 2008
?'-Io
Rough Plumbing I Insulation Inspe
Office No. (518) 761-8256
Queensbury Building & Code Enforcement
742 Bay Road, Queensbury, NY 12804
---x;e~
Ion Rep&'rt
ived: ~,:
art: ~ :.~
"
NAME: HrJckov-- ~e:(~
LOCATION: '1 (
TYPE OF STRUCTURE:
20/0 ~COr.
I-.~-./Q
Nail Plates
Plu' Vents in Place
1 % inch minimum Drain Size
. Drain 2 inch minimum
Cleanout eve 100 feet I chan e of direction
Pressure Test
Drain I Vent
Air I Head
5 P.S.I. or 10 ft. above hi hest connection for 15 minutes
Pressure Test
Water Supply Piping
Air I Head
50 P .S.I for 15 minutes
Insulation I Residential Check I Commercial Check
T ek or Similar Exterior Sealant
Pro r Vent, Attic Vent
Door I Window Sealed No Insulation
Duct I Hot Water Piping Insulation
If uired unheated aces
Combustion Air Su for Furnace
Duct work sealed fO ert I No duct ta e
_~ "'\"0
..J t=:c::.v "- \
v~~\F'
~9~~
L-c:>~~ ~'='~
~~,~ t:>~~.
COMMENTS:
Rough Plumbing Insulation Reportrevised Noy 172003, revised February 15, 2005, revised January 7, 2008
?- /0 ~Rtr
Framing I Firestopping Inspection Repq
Office No. (518) 761--8256
Queensbury Building & Code Enforcement
742 Bay Road, Queensbury, NY 12804
~~~~fi~5
TYPE OF STRUCTURE:
/' '"
y \ y [/'N N1A
( Frami~ D~tw\\h~_ ./
I'\me I'\CC8SS 22- x '30- minimum
Jack Studs I Headers
Bracing I Bridging
Joist hangers
Jack Posts I Main Beams
Exterior sheeting nailed properly
12- O.C.
Headroom 6 ft. 8 in.
Stairwells 36 in. or more
Exterior Deck Bracing
Headroom 6 ft. 8 in. .
Notches I Holes I Bearing Walls
Metal Strapping for Notches Top Plate
1 % (w) 16 aauge (8) 160 nails each aide
Draft stopping 1,000 sq. ft. floor trusses
Anchor Bolts 6 ft. or less on center
Ice and water shield 24 inches from wall
Fire separation 1, 2, 3 hour
Fire wall 2, 3, 4 hour
Firestopping
Penetration sealed
16 inch insulat~on in cavity min.
Garage Fire Separation
House side % inch or 518 inch Type X
Garage side 5/8 inch Type X
Ceilinalwall
Windows Habitable Space I Bedrooms
24 in. (H)
20in.~
5.7 sf above I below grade
5.0 sf grade
/ves~.
.
n; -q:5Q~
PERMIT #:
INSPECT ON:
2o/() -OOt?'
1-/f',./rJ
I ,
COMMENTS:
L:\Building & Codes Forms-OlD\8ulIdIng & Codes\lnspectlon FOfJN\Freming Fn.topplng Inspec:;tion Repott.doc Reviled JInutIry 7,2008
Office No. (518) 761-8256
Queensbury Building & Code Enforcement
742 Bay Road, Queensbury, NY 12804
c lose- TO j G ~ {() - l?--
Rough Plumbing I Insulation Inspection Report
(MId: ltr~b
part: '217'1> a [D../ __
d ulO ,- OO/~/
I )) '-'//1 tJ
I
NAME:J J~ S~ ? fl-t) f)&V1IVS i~ 11A NefiLiJ.t!- PERMI
LOCATION: Cf C l+r f i ,e.{). INSPECT ON:
TYPE OF STRUCTURE:
y N N/A
-
Rouah Plumbing I Nail Plates
Plumbina Vent I Vents in Place
1 % inch minimum Drain Size
Washina Machine Drain 2 inch minimum
Cleanout every 100 feet I change of direction
Pressure Test
Drain I Vent
Air I Head
5 P .S.I. or 10ft. above hiahest connection for 15 minutes
Pressure Test
Water Supply Piping
Air I Head /'
I/' 50 P.SJ for 15 minutes
~ Insulation I Residential Check I Commercial Check V
Tyvek or Similar Exterior Sealant
Proper Vent, Attic Vent
Door I Window Sealed (No Insulation)
Duct I Hot Water Piping Insulation
If reauired unheated spaces
Combustion Air Supply for Furnace
Duct work sealed properly I No duct tape
~~Z-'
~\~~
6?rc~cx.
W~
COMMENTS:
Rough Plumbing Insulation Reporlrevised Nov 172003, revised February 15, 2005, revised January 7, 2008
c ((J ~e 7 ()\ L-ft-t / 0 ~ ("L-
Framing I Firestopping Inspection Report
. . J/;)/~tJ
rt;~~
?
Office No. (518) 761-8256
Queensbury Building & Code Enforcement
742 Bay Road, Queensbury, NY 12804
vd 54\ f-lt44 dU14 fr S' /~ (It, lVe
NAME:
LOCATION:
TYPE OF STRUCTURE:
/"
~ ~ ./I Y N N1A
~raming ~ h ~~ _() \ nCl-- VW'--r:- ,'1
'>'"
Attic Access 22- x 30- minimum I
Jack Studs I Headers
Bracing I Bridging
Joist hangers
Jack Posts I Main Beams
Exterior sheeting nailed properly
12- a.c.
Headroom 6 ft. 8 in.
Stairwells 36 in. or more
Exterior Deck Bracing
Headroom 6 ft. 8 in. .
Notches I Holes I Bearing Walls
Metal Strapping for Notches Top Plate
1 % (w) 16 aauae (8) 160 naBs each side
Draft stopping 1,000 sq. ft. floor trusses
Anchor Bolts 6 ft. or less on center
Ice and water shield 24 inches from wall
Fire separation 1, 2, 3 hour
Fire wall 2, 3, 4 hour
Firestopping
Penetration sealed
16 inch insulat~on in cavity min.
Garage Fire Separation
House side % inch or 518 inch Type X
Garage side 5/8 inch Type X
Ceilinalwall
Windows Habitable Space I Bedrooms
24 in. (H)
20in.~
5.7 sf above I below grade
5.0 sf grade
~PERM'T #:
INSPECT ON:
2o/b-tLJ~
~/ 11/"0
COMMENT~:
9\\~\ \\"-.
L:\Buildlng & Codes FOI'I'JIs-<>lD\Bulld1ng & Codes\lnapection Forma\Framing FireItoppIng Inspedion Report.doc Reviled Januery 7,2008
Foundation Inspection Report
Office No. (518) 761-8256
Queensbury Building & Code Enforcement
742 Bay Rd., Queensbury, NY 12804
j) a vc--
Date Inspection request received:
Arrive: am/~IJ Depart:
Inspector's Initials: ~
am/pm
NAME: -I!:t.k,"-.- ~<..J~rs PERMIT#: 1010 - 60g
LOCATION: 'An; ~ INSPECT ON: ~ i-/C:-jO
TYPE OF STRU :
-
V I \ y ./ N N1A
~Ootings ) ,/
Piers--
Monolithic Slab
Reinforcement in Place
The contractor is responsible for
providing protection from freezing
for 48 hours following the placement
of the concrete.
Materials for this Duroose on site.
Foundation I Wallpour
Reinforcement in Place
Footing Dowels or Keyway in place
Foundation Dampproofing
Foundation Waterproofing
Footing Drain Daylight or Sump
Footing Drain Stone:
12 inch width
6 inches above footing
6 mil oolv for wet areas under slab
Backfill Approval
Plumbing Under Slab
PVC I Cast I Copper
Foundation Insulation Interior I Exterior
R-
Rough Grade 6 inch drop within 10ft.
Comme.~
Ilecfevcf J/J
Lt.!/IC-/t. It ~rb
L:\Bulldlng &. Codes Forms\Building &. Codes\Inspectlon Forms\Foundatlon Inspection Report.doc
Last: printed 12/20/20059:24:00 AM
P<< vie
Foundation Inspection Report
Office No. (518) 761-8256
Queensbwy Building & Code Enforcement
742 Bay Rd., Queensbury, NY 12804
Date Ins~tion request received:
Arrive: )'')u am/~1 t. Depart:
Inspector's Initials:.~
am/pm
NAME' -!!!!!t~ Ik~
LOCATION: . .
TYPE OF STRUCTURE:
PERMIT #:
INSPECT ON:
, P't$~if=
2o/0-CX1;
Comme.~
~
( /~ Y N N.1A
Footings )
Ji"iers ~
Monolithic Slab
Reinforcement in Place
The contractor is responsible for
providing protection from freezing
for 48 hours following the placement
of the concrete.
Materials for this DUfOOse on site.
Foundation I Wallpour
Reinforcement in Place
Footing Dowels or Keyway in place
Foundation Dampproofing
Foundation Waterproofing
Footing Drain Daylight or Sump
Footing Drain Stone:
12 inch width
6 inches above footing
6 mil DOlv for wet areas under slab
Backfill Approval
Plumbing Under Slab
PVC I Cast I Copper ~
Foundation Insulation Interior I Exterior V
R- IO
Rough Grade 6 inch drop within 10ft.
ole -k f~U" T/""., 6'1~
L:\Bullding & Codes Forms\Building & Codes\Inspection Fonns\Foundatlon Inspection Report.doc
Last printed 12/20/2005 9:24:00 AM
-2 .'00 tJeJt~
Queensbury Building & Code Enforcement - Residential ~
/' ;,!
Office No. (518) 761-8256 Arrive: \/,h~ a
Date Inspection request received: _ Inspect~s:
NAME: HvcJ.~ -11;:4' ?J;:s
LOCATION: I 'J?
TYPE OF STRUCTURE: - ~.
spection
~: 7-~m~
20ft) -OO;P
- 2 - S-:-~LO
Comments:
'i_ No N/A
4" Suildlna Number Address visible from road
Chimney Heiaht I"S" Vent/Direct Vent Location
Fresh Air Intake /
3 inch Plumbina Vent throuah roof minimum 6 inches //
Roof Comol. I Exterior Finish ComOlete "~
Platform at all exterior doors ./
Handrail 4 or more risers -
Guards at stairs decks Datios more than 30 inches above arade
Guard at stairwell at 34 inches or more
Guard at deck, porches 36 inches or more
Handrail Termination at Newell Post or Wall
InteriorlExterior Railinas 34 inches to 38 inches
Deck Bradna I Handicapped RamD ComDliant
Grade away from foundation 6 inches with 10 feet .
6 inch clearance to sill plate 1/
Gas Valve shut-off exDoSed I reaulator 18 inches above arade I
Interior orivacv I trim I doors I main entrance 36 inches Uv
Bathroom I Kitchen watertiaht
SafetY alazina I Window in stairwells safetv- alazina
Interior Smoke Detectors I Carbon Monoxide Detectors
Everylevel: _ Every Bedroom: _
Outside every bedroom ares: _
Inter Connected: BatteN backuo:
Attic access 30 inches x 22 inches x 30 inches (haiaht) in accessible area
Crawl Soaces 18 inch x 24 Inch access 1 sa. ft.-150 sa. ft. vents
Bathroom Fans. if no window
Plumbina fixtures
Foundation insulation 'Insulation Certification
Floor truss, draft stoDDina finished basement 1,000 sa. ft.
Emeraencv earess below ~rade
Gas Furnace shut-off within 30 feet or within line of site
Oil Furnace shut-off at entrance to furnace area
Furnace/Hot Water Heater ooeratina
Low water shut-off boiler
Relief Valve(s) installed I Heat TraD! Water Temo 110
Enclosed Stairs Sheetrock Underside minimum W Gvosum
Basement stairs closed rise> 4 inches
Garaae Floor Pitched
Garaae fireorooflna I % hour fll'e door I door closer
Duct work Seal8d orooerlv /
Gas Loa. in Sealed or Glass Enclosure ~
Final Electrical v
Final Survey Plot Plan
Arc Fault Breaker in Bedrooms
Flex Gas Pice Bonding /
As Built Seotic System I Sewer DeDt. 'nscection Sticker /
Site Plan 'Variance reauired ----- -", /
Flood Plain Certification, ifreauired ./' J /
Okay to issue C I C or C , 0 r Temoorarv.J1>ermanent ~ V
~
- LD't\.~
~~ \ ~~f\Ll.\\ir
'\bCY~-~ ~ \-\ t\~~~~
L:\Building & Codes Forms\Building & Codes\lnspection Forms\Residential Final Inspection Form_revised_100405.doc; Revised
January 7 I 2008; Revised 6126108
evergreen
TESTING & ENVIRONMENTAL SERVICES, INC. 594 Broadway Watervliet, NY 12189 Phone: 518-266-0310 Fax: 518-266-9238
CONCRETE FIELD OBSERVATION REPORT
PROJECT: Hudson Headwaters Health Network CLIENT: RE Jones Associates Architects REPORT NO: E-10-02-1-05-10
CONTRACTOR: TMG CONCRETE SUPPLIER: elF DATE: 1-05-10
LOCATION: Vacant north end building floor SOG JOB NO: ETE-10-02
TIME WATER (GALLONS)
Load Ticket Truck Cubic Slump Air % Cone. Mix No.
No. No. No. Yards (in.) Temp Air Temp. Set No.
Batched Start Empty Agg. Added: Total Design out! Remarks
Plant Total in
+ Field
1 6044454 205 10.5 0732 0812 0900 5.0 24/40 1.5 68 1013-12 Set 1 of 6 cyls
4 6044457 205 10.5 1042 1125 1220 7.5 25/42 I.7 64 1013-12 Set 2 of 6 cyls
COMPRESSIVE STRENGTH DATA
SET LA BORA TORY DATE DATE UNIT WT. AGE COMPRESSIVE
NO. NO. RECEIVED TESTED OF CYL. (Days) STRENGTH (psi)
AS RECEIVED
1,2 9307 9313 1-07-10 1-12-10 150.3 150.0 7 3530 3390
9308 9314 1-12-10 149.8 149.3 7 3350 2950
9309 9315 2-02-10 150.5 149.0 28
9310 9316 2-02-10 149.0 148.8 28
9311 9317 149.8 149.5 H
9312 9318 149.5 149.5 H
Tested By: JSC
Field Results Reported to: Smitty
of TMG
Transported By:
Remarks: Placement under heated
building area. Set 1-east end, set
2-west of center
Weather: Overcast
Specification at 28 Days: 4K
Average 28 Day Strength:
Average 56 Day Strength:
Richard E. Jones Associates
Architects - Environmental Planners
339 Aviation Road
Queensbury, NY 12804
Phone: (518) 793-1015 Fax: (518) 793-2223
E-mail: info@rejaarchitects.com
Letter of Completion
February 10, 2010
Town of Queensbury Building Department
742 Bay Road
Queensbury, NY 12804
Re: Hudson Headwaters Health Network
Office fit-up - 9 Carey Road
Building Permit #2010-008
To Whom It May Concern:
To the best of my knowledge and belief, the construction of the above referenced project with Building
Permit '-2010-008 has been completed per the submitted and approved plans and conforms to the
required BuDding Codes of New York State.
Should you have any questions with regard to this Letter of Completion do not hesitate to contact me.
Sincerely,
R~
Richard E. Jones, AI
Cc: File
TMG, LLC
HHHN
\ \ Ts-htgl170\shae 1 \01 - Projects\axJ9\09Q9\Regulatay Agency\letter of completion.doc
evergreen
TESTING & ENVIRONMENTAL SERVICES, INC. 594 Broadway Watervliet, NY 12189 Phone: 518-266-0310 Fax: 518-266-9238
CONCRETE FIELD OBSERV A TION REPORT
PROJECT: Hudson Headwaters Health Network CLIENT: RE Jones Associates Architects REPORT NO: E-10-02-1-05-10
CONTRACTOR: TMG CONCRETE SUPPLIER: elF DATE: 1-05-10
LOCA TION: Vacant north end building floor SOG JOB NO: ETE-10-02
TIME WATER (GALLONS)
Load Ticket Truck Cubic Slump Air % Cone. Mix No.
No. No. No. Yards (in.) Temp Air Temp. Set No.
Batched Start Empty Agg. Added: Total Design out! Remarks
Plant Total in
+ Field
1 6044454 205 10.5 0732 0812 0900 5.0 24/40 1.5 68 1013-12 Set 10f 6 cyls
4 6044457 205 10.5 1042 1125 1220 7.5 25/42 1.7 64 1013-12 Set 2 of 6 cyls
COMPRESSIVE STRENGTH DATA
SET LABORA TORY DATE DATE UNIT wr. AGE COMPRESSIVE
NO. NO. RECEIVED TESTED OF CYL. (Days) STRENGTH (psi)
AS RECEIVED
1,2 9307 9313 1-07-10 1-12-10 150.3 150.0 7 3530 3390
9308 9314 1-12-10 149.8 149.3 7 3350 2950
9309 9315 2-02-10 150.5 149.0 28 4280 4370
9310 9316 2-02-10 149.0 148.8 28 4140 4350
9311 9317 149.8 149.5 H
9312 9318 149.5 149.5 H
-
Tested By: JSC
Field Results Reported to: Smitty
of TMG
Transported By:
Remarks: Placement under heated
building area. Set 1-east end, set
2-west of center
Weather: Overcast
Specification at 28 Days: 4K
Average 28 Day Strength: 4210/4360
Average 56 Day Strength:
--------- ---
Commercial Final Inspection Report
Office No.: (518) 761-8256
Queensbury Building & Code Enforcement
742 Bay Road, Queensbury, NY 12804
NAME: \"h.)\),t.,~ \-\~A-\F~j,
LOCATION: LA e.t~ Qt::>
Date Inspection r
Arrive:
Inspector's InitIa s'
COMMENTS:
y N NA
Chimney / "B" Vent / Direct Vent Location
Plumbing Vent Through Roof 6" / Roof Complete
Exterior Finish / Grade Complete 6" in 10' or Equivalent
Interior / Exterior Guardrails 42 in. Platform / Decks
--
Interior / Exterior Ballisters 4 in. Spacing Platform / Decks
Stair Handrail 34 in. - 38 in. / Step Risers 7" / Treads 11"
Vestibules For Exit doors> 3000 sq. ft.
All Doors 36 in. w/Lever Handles / Panic Hardware, if required
Exits At Grade Or Platform 36 (w) x 44" (l)/Canopy or EQuiv.
Gas Valve Shut-off Exposed & Regulator (18") Above Grade
Floor Bathroom Watertight / Other Floors Okay
Relief Valve, Heat Trap / Water Temp. 110 Degrees Maximum
Boiler / Furnace Enclosure 1 hr. or Fire Extinguishing System
Fresh Air Supply for Occupancy / Ventilation Combustion
Low Water Shut Off For Boilers
Gas Furnace Shut Off Within 30 ft. or Within Line Of Site
Oil Furnace Shut Off at Entrance to Furnace Area
Stockroom/Storage/Receiving/Shipping Room (2 hr.), 1 12 doors
> 10% > 1000 sq. ft.
% Hour Corridor Doors & Closers
Firewalls / Fire Separation, 2 Hour, 3 Hour Complete / Fire
Dampers / Fire Doors
Ceiling Fire Stopping, 3,000 sq. ft. Wood Frame
Attic Access 30" x 20" x 30" (h), Crawl Space Access 18" x 24"
Smoke Vents Or Fan, if required
Elevator Operation and Signage / Shaft Sealed
Handicapped Bathroom Grab Bars / Sinks / Toilets
Handicapped Bath / Parkine Lot Sienaee
Public Toilet Room Handicapped Accessible
Handicapped Service Counters, 34 in., Checkout 36" /
Handicapped Ramp / Handrails Continuous/12 in. Beyond (Both sides] I
Active Listening System and Signage Assembly Space /
Final Electrical V
Site Plan / Variance required
Final Survey, New Structure / Flood Plain certification, if reQ.
As-built Septic System Layout Required or On File
Building Number or Tenant Address on Building or Driveway 1/
Water Fountain or Cooler j
Building Access All Sides bv ')(\' Ie Surface 20' wide /
Okay To Issue Temp..Jl'I'1iermanent C/O ') J
Okay To Issue C/C (
L:\Building & Codes Forms\Building & Codes\Inspection Forms\Commercial Final Inspection Report.doc
COMMONWEALTH ELEC
Main Office 176 DoeT~C:O~dIN~PE;!ION SERVICE, INC.
MUNICIPAL CERTIFICATE - ELE~;'i';~tt1~PROVAL
Pennit No........................................Cert. N~ . 10067 Cut-in Card No
Owner.....Ih:!..O'5.?l (j /I.. e-1112lt.i 4~#1. .....................................
9 {'11..... .......... ............. ........~...........................$.". ~c..TH-
L . ~ ""Y AZ .....................................................
t ~ ........
oca IOn ..................................~.. .................'12....:... ....................... a...~~
Ulu~ ~~~nn Or..Zr!.Qi}l.~r;i(gt~,~..................:.::.
d" N' ~~ F/l-u;- tEQ~ P ~J~...........................................
.............................~.......................................................................................................
..............................................................................~..................................~.~~..~::.:::::::::::::::::::::::..:::..................:....:...................
Installed BY.....2..:...r.1J...$..:..K..tI.:f..u...&:./!............................ . ..'
The conditions following governed the issuance of this certificate, and any certificate previously Issued IS
cancelled: - . . t and installation conditions as of date. Upon the
This certificate only covers the electncal eqUlpmenl" t' n shall be promptly made for inspection.
introduction of additional eqUIpment or alterathlOns, apr Ica I; making inspections at any time, and if its
lns ectors of this Company shall have t e pnvl ege 0 .~
rules ar~ violated, the Company shall have the right to r~vok~hIS rt Icate. ..............................
2-- -( b .-/0 INSPECTOR .......~.~... .....................................
Date.................................................. Member N.F.P.A., I.A.E.I.
2010 -(X::fB'
COMcheck Software Version 3.6.1
Envelope Compliance Certificate
2007 New York Energy Conservation Construction Code
Section 1: Project Information
Project Type: Addition
Project Title: HHHN Office Building
Construction Site:
9 Carey Road
Queensbury, NY 12804
Owner/Agent:
George Purdue
Hudson Headwaters Health Network
PO Box 357
9 Carey Road
Glens Falls, NY 12801
761-0300 x 114
Section 2: General Information
Building Location (for weather data):
Climate Zone:
Heating Degree Days (base 65 degrees F):
Cooling Degree Days (base 65 degrees F):
Vertical Glazing I Wall Area Pet.:
Warren, New York
15
7635
366
15%
Building Type
Office
Floor Area
5358
Section 3: Requirements Checklist
Designer/Contractor:
Richard Jones
Richard E. Jones Associates Architects
339 Aviation Road
Queensbury, NY 12804
793-1015
Climate-Specific Requirements:
Envelope PASSES Design 22'Yo better than code.
Component Name/Description
Gross Area
or Perimeter
5358
2592
Roof 1: All-Wood JoistlRafterlTruss
Exterior Wall 1 : Wood Frame, Any Spacing
Cavity
R-Yalue
38.0
19.0
Cont.
R-Yalue
0.0
0.0
Proposed
U-Factor
0.028
0.068
Budget
U-Factor
0.051
0.074
o 7 Cargo doors and loading dock doors are weather sealed.
o 8. Recessed lighting fixtures are: (i) Type IC rated and sealed or gasketed; or (ii) installed inside an appropriate air-tight assembly with a
0.5 inch clearance from combustible materials and with 3 inches clearance from insulation material.
o 9. Vapor retarder installed.
Section 4: Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed envelope system has been designed to meet the 2007 New York
Energy Conservation Construction Code requirements in COMcheck Version 3.6.1 and to comply with the mandatory requirements in the
Requirements Checklist.
When a Registered Design Professional has stamped and signed this page, they are attesting that to the best of hislher knowledge, belief, and
professional judgment, such plans or specifications are in compliance with this Code. ..-:1' .....,
. /J ./~ i/
I ,(/ .'l- j,'
~t{jJITt'f.1" . {t(./ tr . /17fL,/
/ Signature I /
l ;'
'j;:'I (.,/,) JI} J.~t:J
Name - Title
1/'71/t/
Dati I
\./
Project Title: HHHN Office Building .Report date: 01/08/10
Data filename: \\Ts-htgI170\share1 \01 - Projects\2006\0622\Regulatoty Agency\Building Department\NYS Energy Compliance Statement.cck
office infill.cck 2.cck Page 2 of 9
COMcheck Software Version 3.6.1
Interior Lighting and Power
Compliance Certificate
2007 New York Energy Conservation Construction Code
Section 1: Project Information
Project Type: Addition
Project Title: HHHN Office Building
Construction Site:
9 Carey Road
Queensbury, NY 12804
Owner/Agent:
George Purdue
Hudson Headwaters Health Network
PO Box 357
9 Carey Road
Glens Falls, NY 12801
761-0300 x 114
Designer/Contractor:
Richard Jones
Richard E. Jones Associates Architects
339 Aviation Road
Queensbury, NY 12804
793-1015
Section 2: General Information
Building Use Description by:
Building TYDe
Office
Floor Area
5358
Section 3: Requirements Checklist
Interior Lighting:
o 1. Total proposed watts must be less than or equal to total allowed watts.
Allowed Watts Proposed Watts Complies
5358 4746 YES
o 2. Exit signs 5 Watts or less per sign.
Exterior Lighting:
o 3. Efficacy greater than 45 lumenslW.
Exceptions:
Specialized lighting highlighting features of historic bUildings; signage; safety or security lighting; low-voltage landscape lighting.
Controls, Switching, and Wiring:
o 4. Independent controls for each space (switch/occupancy sensor).
Exceptions:
Areas designated as security or emergency areas that must be continuously illuminated.
Lighting in stairways or corridors that are elements of the means of egress.
o 5. Master switch at entry to hotel/motel guest room.
o 6. Individual dwelling units separately metered.
o 7. Each space provided with a manual control to provide uniform light reduction by at least 50%.
Exceptions:
Only one luminaire in space;
An occupant-sensing device controls the area;
The area is a corridor, storeroom, restroom, public lobby or guest room;
Areas that use less than 0.6 Watts/sq.ft.
o 8. Automatic lighting shutoff control in buildings larger than 5,000 sq.ft.
Exceptions:
Project Title: HHHN Office Building Report date: 01/08110
Data filename: \\Ts-htgl17O\share1\01 - Projects\2006\0622\Regulatoty Agency\Building DepartmentlNYS Energy Compliance Statement.cck
office infill.cck 2.cck Page 3 of 9
Areas with only one luminaire, corridors, storerooms, restrooms, or public lobbies.
D 9. Photocell/astronomical time switch on exterior lights.
Exceptions:
Lighting intended for 24 hour use.
D 10. Tandem wired one-lamp and three-lamp ballasted luminaires (No single-lamp ballasts).
Exceptions:
Electronic high-frequency ballasts; Luminaires on emergency circuits or with no available pair.
D 11. Transformers meet minimum efficiencies listed in Table 805.6.1 or 805.6.2.
Section 4: Compliance Statement
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2007 New York
Energy Conservation Construction Code requirements inCOMcheck Version 3.6.1 and to comply with the mandatory requirements in the
Requirements Checklist.
1 tt("jJ~t-l-yJ ,1."I.-Jf.4 A ,J;'''''JPT
~ame _ Title v I '
?~
/ -(
t(1.e~/ c:; ~
Signature / /
(/
/ /7/' V
Date / /
Project Title: HHHN Office Building Report date: 01/08110
Data filename: \\Ts-htgl17O\share1\01 - Projects\2006\0622\Regulatoty Agency\Building DepartmentlNYS Energy Compliance Statement.cck
office infill.cek 2.eek Page 4 of 9
COMcheck Software Version 3.6.1
Interior Lighting Application
Worksheet
2007 New York Energy Conservation Construction Code
Section 1: Allowed Lighting Power Calculation
A
BCD
Floor Area Allowed Allowed Watts
Watts / ft2
5358 1 5358
Total Allowed Watts = 5358
Office
Section 2: Proposed Lighting Power Calculation
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
BCD E
Lamps/ # of Fixture (C X D)
Linear Fluorescent 1: C: 2x4 parabolic lay in / 48" T8 32W / Electronic
Linear Fluorescent 2: B: 2x2 parabolic lay in /24" T8U 32W / Electronic
Linear Fluorescent 3: D: 1x4 surface /48" T8 32W I Electronic
Linear Fluorescent 4: A: 8' cable hung I 48" T8 32W / Electronic
3 13 96 1248
2 5 34 170
2 6 64 384
4 23 128 2944
Total Proposed Watts = 4746
Section 3: Compliance Calculation
If the Total Allowed Watts minus the Total Proposed Watts is greater than or equal to zero, the building complies.
Total Allowed Watts = 5358
Total Proposed Watts = 4746
Project Compliance = 612
Interior Lighting PASSES DeSign 11 % better than code.
Project Title: HHHN Office Building Report date: 01/08110
Data filename: \\Ts-htgI170\share1\01 - Projects\2006\0622\Regulatoty Agency\Building Department\NYS Energy Compliance Statement.cck
office infill.cck 2.cck Page 5 of 9
COMcheck Software Version 3.6.1
Mechanical Compliance Certificate
2007 New York Energy Conservation Construction Code
Section 1: Project Information
Project Type: Addition
Project Title: HHHN Office Building
Construction Site:
9 Carey Road
Queensbury, NY 12804
Owner/Agent:
George Purdue
Hudson Headwaters Health Network
PO Box 357
9 Carey Road
Glens Falls, NY 12801
761-0300 x 114
Designer/Contractor:
Richard Jones
Richard E. Jones Associates Architects
339 Aviation Road
Queensbury, NY 12804
793-1015
Section 2: General Information
Building Location (for weather data):
Climate Zone:
Heating Degree Days (base 65 degrees F):
Cooling Degree Days (base 65 degrees F):
Warren, New York
15
7635
366
Section 3: Mechanical Systems List
Quantity System Type & DescriDtion
2 HVAC System 1: Rooftop Packaged Heat Pump, Heat Capacity 120 kBtu/h Cool Capacity 113 kBtu/h,
Air-Cooled Condenser / Single Zone
Section 4: Requirements Checklist
Requirements Specific To: HVAC System 1 :
o 1. Equipment minimum efficiency: Heat Pump: 3.2 COP 10.1 EER
o 2. Heat pump thermostat required when supplemental electric resistance heat is installed
o 3. Integrated air economizer required
Generic Requirements: Must be met by all systems to which the requirement is applicable:
o 1. Load calculations per 2001 ASHRAE Fundamentals
o 2. Plant equipment and system capacity no greater than needed to meet loads
- Exception: Standby equipment automatically off when primary system is operating
- Exception: Multiple units controlled to sequence operation as a function of load
o 3. Minimum one temperature control device per system
o 4. Minimum one humidity control device per installed humidification/dehumidification system
o 5. Automatic Controls: Setback to 55 degrees F (heat) and 85 degrees F (cool); 7-day clock, 2-hour occupant override, 10-hour backup
- Exception: Continuously operating zones
- Exception: 2 kW demand or less, submit calculations
o 6. Automatic shut-off dampers on exhaust systems and supply systems with airflow >3,000 cfm
o 7. Outside-air source for ventilation; system capable of reducing OSA to required minimum
o 8. R-5 supply and return air duct insulation in unconditioned spaces R-8 supply and return air duct insulation outside the building R-8
insulation between ducts and the building exterior when ducts are part of a building assembly
- Exception: Ducts located within equipment
Project Title: HHHN Office Building Report date: 01/08110
Data filename: IITs-htgl170lshare1 \01 - Projects\2006\0622\Regulatoty Agency\Building DepartmentlNYS Energy Compliance Statement.cck
office infill.cck 2.cck Page 6 of 9
- Exception: Ducts with interior and exterior temperature difference not exceeding 15 degrees F.
o 9. Ducts sealed -longitudinal seams on rigid ducts; transverse seams on all ducts; UL 181A or 181B tapes and mastics
Exception: Continuously welded and locking-type longitudinal joints and seams on ducts operating at static pressures less than 2
inches ..v.g. pressure classification
o 10. Mechanical fasteners and sealants used to connect ducts and air distribution equipment
o 11. Operation and maintenance manual provided to building owner
o 12. Balancing devices provided in accordance with 603.15 of Mechanical Code for New York State
o 13. Stair and elevator shaft vents are equipped with motorized dampers
Section 5: Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed mechanical systems have been designed to meet the 2007 New
York Energy Conservation Construction Code requirements in COMcheck Version 3.6.1 and to comply with the mandatory requirements in the
Requirements Checklist.
-, /
"// .{/i
C {J!.. ~/ ( . l2kz./
Signature '/
iF
(/7 )10
Date I
Project Title: HHHN Office Building Report date: 01/08110
Data filename: \\Ts-htgl170\share1\01 - Projects\2006\0622\Regulatoty Agency\Building Department\NYS Energy Compliance Statement.cck
office infill.cck 2.cck . Page 7 of 9
COM check Software Version 3.6.1
Mechanical Requirements
Description
2007 New York Energy Conservation Construction Code
The following list provides more detailed descriptions of the requirements in Section 4 of the Mechanical Compliance
Certificate.
Requirements SpeCific To: HVAC System 1 :
1. The specified heating and/or cooling equipment is covered by the 2007 New York Energy Conservation Construction Code and must
meet the following minimum efficiency: Heat Pump: 3.2 COP 10.1 EER
2. Heat pumps having supplementary electric resistance heat must have controls that, except during defrost, prevent supplementary heat
operation when the heat pump can meet the heating load.
3. An integrated air economizer is required for individual cooling systems over 65 kBtu/h in the selected climate. An integrated economizer
allows simultaneous operation of outdoor-air and mechanical cooling.
Generic Requirements: Must be met by all systems to which the requirement is applicable:
1. Design heating and cooling loads for the building must be determined using procedures in the ASHRAE Handbook of Fundamentals or
an approved equivalent calculation procedure.
2. All equipment and systems must be sized to be no greater than needed to meet calculated loads. A single piece of equipment providing
both heating and cooling must satisfy this provision for one function with the capacity for the other function as small as possible, within
available equipment options.
- Exception: The equipment and/or system capacity may be greater than calculated loads for standby purposes. Standby equipment
must be automatically controlled to be off when the primary equipment and/or system is operating.
Exception: Multiple units of the same equipment type whose combined capacities exceed the calculated load are allowed if they are
provided with controls to sequence operation of the units as the load increases or decreases.
3. Each heating or cooling system serving a single zone must have its own temperature control device.
4. Each humidification system must have its own humidity control device.
5. The system or zone control must be a programmable thermostat or other automatic control meeting the following criteria: a) capable
of setting back temperature to 55 degrees F during heating and setting up to 85 degrees F during cooling, b) capable of automatically
selting back or shutting down systems during unoccupied hours using 7 different day schedules, c) have an accessible 2-hour occupant
override, d) have a battery back-up capable of maintaining programmed settings for at least 10 hours without power.
Exception: A setback or shutoff control is not required on thermostats that control systems serving areas that operate continuously.
- Exception: A setback or shutoff control is not required on systems with total energy demand of 2 kW (6,826 Btu/h) or less.
6. Outdoor-air supply systems with design airflow rates >3,000 cfm of outdoor air and all exhaust systems must have dampers that are
automatically closed while the equipment is not operating.
7. The system must supply outside ventilation air as required by Chapter 4 of the Mechanical Code for New York State. If the ventilation
system is designed to supply outdoor-air quantities exceeding minimum required levels, the system must be capable of reducing
outdoor-air flow to the minimum required levels.
8. Air ducts must be insulated to the following levels: a) Supply and return air ducts for conditioned air located in unconditioned spaces
(spaces neither heated nor cooled) must be insulated with a minimum of R-5. Unconditioned spaces include attics, crawl spaces,
unheated basements, and unheated garages. b) Supply and return air ducts and plenums must be insulated to a minimum of R-8 when
located outside the building. c) When ducts are located within exterior components (e.g., floors or roofs), minimum R-8 insulation is
required only between the duct and the building exterior.
Exception: Duct insulation is not required on ducts located within equipment.
Exception: Duct insulation is not required when the design temperature difference between the interior and exterior of the duct or
plenum does not exceed 15 degrees F.
9. All joints, longitudinal and transverse seams, and connections in ductwork must be securely sealed using weldments; mechanical
fasteners with seals, gaskets, or mastics; mesh and mastic sealing systems; or tapes. Tapes and mastics must be listed and labeled in
accordance with UL 181AorUL 181B.
Exception: Continuously welded and locking-type longitudinal joints and seams on ducts operating at static pressures less than 2
inches w.g. pressure classification.
10. Mechanical fasteners and seals, mastics, or gaskets must be used when connecting ducts to fans and other air distribution equipment,
including multiple-zone terminal units.
11. Operation and maintenance documentation must be provided to the owner that includes at least the following information: a) equipment
capacity (input and output) and required maintenance actions b) equipment operation and maintenance manuals c) HVAC system
Project Title: HHHN Office Building Report date: 01/08110
Data filename: \\Ts-htgl170\share1\01 - Projects\2006\0622\Regulatoty Agency\Building Department\NYS Energy Compliance Statement.cck
office infilLcck 2.cck Page 8 of 9
control maintenance and calibration information, including wiring diagrams, schematics, and control sequence descriptions; desired
or field-detennined set points must be pennanently recorded on control drawings, at control devices, or, for digital control systems, in
programming comments d) complete narrative of how each system is intended to operate.
12. Each supply air outlet or diffuser and each zone tenninal device (such as VAV or mixing box) must have its own balancing device.
Acceptable balancing devices include adjustable dampers located within the ductwork, terminal devices, and supply air diffusers.
13. Stair and elevator shaft vents must be equipped with motorized dampers capable of being automatically closed during normal building
operation and interlocked to open as required by fire and smoke detection systems. All gravity outdoor air supply and exhaust hoods,
vents, and ventilators must be equipped with motorized dampers that will automatically shut when the spaces served are not in use.
Exception: Gravity (non-motorized) dampers are acceptable in buildings less than three stories in height above grade.
- Exception: Ventilation systems serving unconditioned spaces.
Project Title: HHHN Office Building Report date: 01/08110
Data filename: \\Ts-htgl17O\share1\01 - Projects\2006\0622\Regulatoty Agency\Building Department\NYS Energy Compliance Statement.cck
office infill.cck 2.cck Page 9 of 9
20/0-CD~
Richard E. Jones Associates
Architects - Environmental Planners
339 Aviation Road
Queensbury, NY 12804
Telephone (518) 793-1015 Fax (518)793-2223
E-mail: richardjones@rejaarchitects.com
Memo
To: Dave Hatin, Town of Queensbury
Date: 01/08/2010
Re: Hudson Headwaters Health Network Office Building (Building Permit for
Office Fit-up)
ADDENDA ITEMS:
1. Attic Access Door:
· Drawing A-2 Reflected Ceiling Plan; Note 2 for attic access doors; Change size to read
22" x3Q".
2. A reviewed and approved copy of the following shop drawing will be provided to the Town
of Queensbury Building Department for their file:
· Fire sprinkler layout drawings including hydraulic design calculations.
3. Drawing ME-1 HVAC Plan, Existing RoofTop Unit Ventilation Design Requirements;
· Air capacity for the two existing RTU's is a nominal 2,900 cfm each.
· The existing RTU's each have integrated economizers that are capable of introducing
100% outside air and will maintain the minimum airflow as required by the Mechanical
Code of NYS into the building during the occupied period providing a design ventilation
rate for full occupancy. The outside air damper for each RTU would not close beyond the
minimums as defined below.
· The outside air damper on the economizer would be set at 14% as a minimum and supply
no less than 400cfm for each unit.
4. Door 1-10 from Open Office 113 to Open Office 114:
· Drawing A-2 Reflected Ceiling Plan; Delete exit sign above door 1-10.
· Drawing A-3 Door Schedule; Change hardware group for Door 1-10 to #2.
· Drawing A-3; Add Hardware Group #2 as follows:
1 Y:z pair hinges
1 communicating lockset with lever handle on Room 114 side & blank
plate on Room 113 side
1 floor stop
· Drawing ME-l Lighting Plan; Delete exit sign above door 1-10 and change exit sign on
north wall of Opened Office # 113 to a single exit direction indication pointing to door 1-18
at rear of building.
\\Ts-htgI170\share1\01 - Projects\2009\0909l8uilding Pennit Memo 10-01-08.doc