CJDR of Qby Final Report of Const Observations signed Structural Civil Municipal DANIEL W. RYAN P.E. Licensed Professional Engineer P.O. Box 596 • Glens Falls, NY • 12801 • (518) 792-9264 www.dwrpe.com April 5, 2021 Town of Queensbury Building & Codes Department 742 Bay Road Queensbury, NY 12804 RE: CJDR of Queensbury Building Addition – 728 Quaker Rd, Queensbury NY 12804 DWRPE assisted with special inspections required for the above project relating to structural work designed by our office and for the PEMB structural frame. Construction observations included; - reinforced concrete work including footings, foundation components, and slabs - structural steel framing and building components for the PEMB per the erection drawings Construction material testing was performed by Construction Technology for soil and concrete, their reports, which were forwarded to our office, are attached for your records. To the best of my information, knowledge, and belief, special inspection and testing required for this project in accordance with Chapter 17 of the 2020 Building Code of NYS have been performed with satisfactory results, and any discovered discrepancies or deficiencies have been resolved. DWRPE also performed periodic construction observation for the above project relating to all other work for the building addition designed, specified, depicted, or designated on construction drawings prepared by our office and used as the basis of issuance of the building permit. To the best of my information, knowledge, and belief, and upon information gathered or obtained during completion of the project and by periodic visible observation of completed work, and with the Contractor being notified of observed discrepancies or deficiencies in observed work for correction, the corresponding project and related work specified for such appears to be in general conformance with plans and specifications prepared for the project. All interim reports and/or project related correspondence or communications prior to this final report form the basis for and are to be considered, by reference, an integral part of this final report. Respectfully submitted: Daniel W. Ryan, P.E. NOTE: Periodic observation means that a representative from our office periodically visited the construction site to observe and verify that visible portions of work at the time of the site visit were constructed in general conformance with project drawings and specifications. Although we attempt to observe all components and/or work of greatest importance, it is noteworthy to state that it is likely that some work or components may not have been observed at all during construction, depending on the timing and frequency of our site visits. This certificate or report does not constitute an acceptance of work completed by the Contractor not in accordance with project or construction drawings, contract documents, or project related specifications, nor is it a release of the Contractor’s obligation to complete all work and ensure all work is in general accordance with all applicable code requirements, the projects technical specifications, and all project related and permit documentation. This certification shall constitute a guarantee or warrantee of any conditions or work, whether explicitly stated or implied. 4 William Street, Ballston Lake, New York 12019 Phone: (518) 399-1848 Email: constructiontech@live.com CLIENT: REPORT NUMBER: : PAGE #: 1 INSPECTION DATE: OUR FILE NUMBER:5 INSPECTOR & TEST SET: DAVE CASAW #5 ATT'N: AMBIENT WEATHER: OUR FILE LOCATION: 1 : PLACEMENT LOCATION OF LOAD # 2 : PLACEMENT LOCATION OF LOAD # 3 : 1 2 0 3 4907 / 844132 4908 / 844133 4903 / 844134 11.00 / 11.00 7 11.00 / 22.00 8 11.00 / 33.00 7.883 6.43 / 6.58 0 ##7.04 / 7.22 0 7.27 / 7.41 0 7.06 / 7.15 # 7 7.24 / 7.33 ##7.43 / 7.53 8.00 MAX: 1.50 )6 0.53 0 7 0.48 0 7 0.43 0 0.43 5.75 7 0.04 5.50 7 0.27 6.00 7 WATER ADDED ONSITE (GALLONS):0.00 0 0.00 0 0.00 0 WATER ADDED AT DISCRETION OF:0.00 # 0.00 ##0.00 0.53 5.75 5.50 6.00 PLACEMENT SLUMP (INCH) (SPEC: - 5.00 )5.75 1 5.50 1 6.00 1 ENTRAINED AIR ( % VOL) (SPEC: - 7.00 ) 5.40 0 0.00 0 0.00 0379600 UNIT WEIGHT (PCF) (SPEC:-0.00 ) 143.78 0 0.00 0 0.00 0 - 90 ) 80 0 79 0 80 0 NUMBER OF TEST SPECIMEN CAST:6 0 0 0 0 205017 - 205022 0 0 0 0 0 0 1: CONCRETE SUPPLIER:CONCRETE TEST CYLINDER COMPRESSIVE RESULTS PER: ASTM: C39 P.S.I. @ 28 DAYS :UNLESS OTHERWISE NOTED ALL CYLINDERS RECEIVED: CEMENT:LBS.CYLINDER TEST UNIT CEMENT:LBS. NUMBER DATE P.S.I. GAL. COARSE AGGREGATE #1: LBS.205017 12/22/20 7 4000 0 COARSE AGGREGATE #2: LBS.205018 12/22/20 7 3790 X COARSE AGGREGATE #3: LBS.205019 01/12/21 28 5610 0 FINE AGGREGATE: LBS.205020 01/12/21 28 5800 0 ADMIXTURE #1: OZS.205021 01/12/21 28 5540 0 ADMIXTURE #2: OZS.205022 01/00/00 SPARE 0 X ADMIXTURE #3: OZS. AIR ENTRAINING AGENT: OZS.0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X REPORT DISTRIBUTION:0 0 0 0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X 0 0 0 01/00/00 0 0 X RESPECTFULLY SUBMITTED,0 0 0 0 01/00/00 0 0 X CONSTRUCTION TECHNOLOGY 0 0 0 0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X ROBERT BEHAN (NICET)0 0 0 0 01/00/00 0 0 X MANAGER TECHNICAL SVCS.0 0 0 0 01/00/00 0 0 X Robert BehanRobert BehanRobert BehanRobert Behan APPLIED LOAD 3 12/15/20 100.202 205017 20's: CLEAR PROJECT: CONSTRUCTION TECHNOLOGY MR. CHARLES ALBRECHT R & P QUAKER II REALTY, LLC 728 QUAKER ROAD QUEENSBURY, NEW YORK 12804 NEMER CHRYSLER JEEP DODGE RAM: QUEENSBURY, NEW YORK CONCRETE TEMP. (F) (SPEC: SLUMP OF CONCRETE INTO PUMP: TIME PLACEMENT BEGAN / ENDED: CONCRETE AGE ( HOURS ) (SPEC: SLUMP ON ARRIVAL (INCHES): IF APPLICABLE: DELIVERED LOAD NUMBER: TRUCK NUMBER / TICKET NUMBER: YARDAGE DELIVERED / SUBTOTAL: LAB CYLINDER CONTROL NUMBERS: WATER: 0 0 DESIGN STRENGTH & FORMULA: 3: TIME CONC. BATCHED / ARRIVED: 50,200 DAYS UNLESS NOTED ALL TESTING IAW: ASTM: C31, C138, C143, C172, C173, C231, C470, C567, C617, C1064 DISCREPANCIES & REMARKS: 0.0 4: 0.0 5: 6: 7: 8: 1: FILE 2: SUPPLIER 47,650 0 0 70,400 69,600 0 0 0 72,850 0 0 0 0 0 0 0 0.0 0 0 0 0 JOINTA-GALUSHA CONCRETE, INC. CONCRETE SLUMP IS AFTER PLASTICIZER ADDITION. ULTIMATE 12/16/20 0.00 C O N C R E T E F I E L D I N S P E C T I O N & C O M P R E S S I O N T E S T R E S U L T S 0.00 TEST AGE 4000 SLAB ON GRADE: WEST PROCEEDING EAST SLAB ON GRADE: WEST PROCEEDING EAST PLACEMENT LOCATION OF LOAD # SLAB ON GRADE: WEST PROCEEDING EAST 0.00 45 PROPER HOT OR COLD WEATHER CURING PROTECTION FOR AMBIENT CONDITIONS IS AVAILABLE ONSITE. PER DRAWING: S-202, DETAIL: 5 GENERAL CONSTRUCTION PRACTICE: CONCRETE PROPERLY CONSOLIDATED. NO VISUAL EVIDENCE OF SEGREGATION OR COLD JOINTS. PLACEMENT AREA REINFORCEMENT: PLACEMENT AREA FORMWORK: ACCEPTABLE FOR ALIGNMENT & CLEANLINESS. FREE OF DEBRIS & STANDING WATER/ICE/SNOW. CLEANLINESS & COVER ACCEPTABLE. PROPERLY SIZED & LOCATED. PLACEMENT WEATHER PROTECTION: 4 William Street, Ballston Lake, New York 12019 Phone: (518) 399-1848 Email: constructiontech@live.com CLIENT: REPORT NUMBER: : PAGE #: 2 INSPECTION DATE: OUR FILE NUMBER:5 INSPECTOR & TEST SET: DAVE CASAW #5 ATT'N: AMBIENT WEATHER: OUR FILE LOCATION: 4 : PLACEMENT LOCATION OF LOAD # 5 : PLACEMENT LOCATION OF LOAD # 6 : 4 5 0 6 4907 / 844135 4908 / 844136 4903 / 844137 11.00 / 44.00 8 11.00 / 55.00 9 11.00 / 66.00 8.85 7.41 / 7.54 0 ##7.53 / 8.07 0 8.09 / 8.22 0 8.00 / 8.15 # 8 8.18 / 8.32 ##8.34 / 8.51 9.00 MAX: 1.50 )7 0.57 0 7 0.65 0 8 0.70 0 0.41 5.75 8 0.53 6.25 8 0.09 5.75 8 WATER ADDED ONSITE (GALLONS):0.00 0 0.00 0 0.00 0 WATER ADDED AT DISCRETION OF:0.00 # 0.00 ##0.00 0.51 5.75 6.25 5.75 PLACEMENT SLUMP (INCH) (SPEC: - 5.00 )5.75 1 6.25 1 5.75 1 ENTRAINED AIR ( % VOL) (SPEC: - 7.00 )0.00 0 5.90 0 0.00 0037560 UNIT WEIGHT (PCF) (SPEC:-0.00 )0.00 0 142.26 0 0.00 0 - 90 ) 78 0 80 0 79 0 NUMBER OF TEST SPECIMEN CAST:0 0 6 0 0 0 0 205023 - 205028 0 0 0 1: CONCRETE SUPPLIER:CONCRETE TEST CYLINDER COMPRESSIVE RESULTS PER: ASTM: C39 P.S.I. @ 28 DAYS :UNLESS OTHERWISE NOTED ALL CYLINDERS RECEIVED: CEMENT:LBS.CYLINDER TEST UNIT CEMENT:LBS. NUMBER DATE P.S.I. GAL. COARSE AGGREGATE #1: LBS.205023 12/22/20 7 3610 X COARSE AGGREGATE #2: LBS.205024 12/22/20 7 3740 X COARSE AGGREGATE #3: LBS.205025 01/12/21 28 5240 0 FINE AGGREGATE: LBS.205026 01/12/21 28 5120 0 ADMIXTURE #1: OZS.205027 01/12/21 28 5270 0 ADMIXTURE #2: OZS.205028 01/00/00 SPARE 0 X ADMIXTURE #3: OZS. AIR ENTRAINING AGENT: OZS.0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X REPORT DISTRIBUTION:0 0 0 0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X 0 0 0 01/00/00 0 0 X RESPECTFULLY SUBMITTED,0 0 0 0 01/00/00 0 0 X CONSTRUCTION TECHNOLOGY 0 0 0 0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X ROBERT BEHAN (NICET)0 0 0 0 01/00/00 0 0 X MANAGER TECHNICAL SVCS.0 0 0 0 01/00/00 0 0 X CONSTRUCTION TECHNOLOGY R & P QUAKER II REALTY, LLC 3 728 QUAKER ROAD 12/15/20 QUEENSBURY, NEW YORK 12804 100.202 MR. CHARLES ALBRECHT 20's: CLEAR PROJECT:NEMER CHRYSLER JEEP DODGE RAM: QUEENSBURY, NEW YORK 205023 C O N C R E T E F I E L D I N S P E C T I O N & C O M P R E S S I O N T E S T R E S U L T S PLACEMENT LOCATION OF LOAD # SLAB ON GRADE: WEST PROCEEDING EAST SLAB ON GRADE: WEST PROCEEDING EAST SLAB ON GRADE: WEST PROCEEDING EAST DELIVERED LOAD NUMBER: TRUCK NUMBER / TICKET NUMBER: YARDAGE DELIVERED / SUBTOTAL: TIME CONC. BATCHED / ARRIVED: TIME PLACEMENT BEGAN / ENDED: CONCRETE AGE ( HOURS ) (SPEC: SLUMP ON ARRIVAL (INCHES): SLUMP OF CONCRETE INTO PUMP: IF APPLICABLE: 0.00 0.00 0.00 CONCRETE TEMP. (F) (SPEC:45 LAB CYLINDER CONTROL NUMBERS: DISCREPANCIES & REMARKS: CONCRETE SLUMP IS AFTER PLASTICIZER ADDITION. PLACEMENT AREA REINFORCEMENT: CLEANLINESS & COVER ACCEPTABLE. PROPERLY SIZED & LOCATED.PER DRAWING: S-202, DETAIL: 5 PLACEMENT AREA FORMWORK: ACCEPTABLE FOR ALIGNMENT & CLEANLINESS. FREE OF DEBRIS & STANDING WATER/ICE/SNOW. GENERAL CONSTRUCTION PRACTICE: CONCRETE PROPERLY CONSOLIDATED. NO VISUAL EVIDENCE OF SEGREGATION OR COLD JOINTS. PLACEMENT WEATHER PROTECTION: PROPER HOT OR COLD WEATHER CURING PROTECTION FOR AMBIENT CONDITIONS IS AVAILABLE ONSITE. UNLESS NOTED ALL TESTING IAW: ASTM: C31, C138, C143, C172, C173, C231, C470, C567, C617, C1064 JOINTA-GALUSHA CONCRETE, INC. DESIGN STRENGTH & FORMULA: 4000 12/16/20 0 TEST AGE ULTIMATE 0 DAYS APPLIED LOAD WATER:0.0 45,300 46,950 65,850 0 64,300 0.0 66,150 0 0 0.0 0 0 0 1: FILE 5:0 2: SUPPLIER 6:0 3:7:0 Robert BehanRobert BehanRobert BehanRobert Behan 0 0 0 4:8:0 0 0 0 4 William Street, Ballston Lake, New York 12019 Phone: (518) 399-1848 Email: constructiontech@live.com CLIENT: REPORT NUMBER: : PAGE #: 1 INSPECTION DATE: OUR FILE NUMBER:5 INSPECTOR & TEST SET: DAVE CASAW #5 ATT'N: AMBIENT WEATHER: OUR FILE LOCATION: 1 : PLACEMENT LOCATION OF LOAD # 2 : 0 0 0 1 2 0 0 4905 / 843732 4598 / 843733 0 0 0 11.50 / 11.50 2 11.50 / 23.00 2 0.00 0 0.00 0 12.40 / 1.06 0 ##1.03 / 1.15 0 0.00 0 0.00 0 1.26 / 1.39 # 1 2.04 / 2.21 ## 0.00 0 0.00 0.00 MAX: 1.50 )12 0.98 0 1 1.30 0 0 0.00 0 0.40 5.50 1 0.03 5.25 2 0.00 0.00 0 WATER ADDED ONSITE (GALLONS):0.00 0 0.00 0 0.00 0 WATER ADDED AT DISCRETION OF:0.00 # 0.00 ##0.00 0.00 5.50 5.25 0.00 PLACEMENT SLUMP (INCH) (SPEC: - 5.00 )5.50 1 5.25 1 0.00 0 ENTRAINED AIR ( % VOL) (SPEC: - 7.00 ) 5.40 0 0.00 0 0.00 0373500 UNIT WEIGHT (PCF) (SPEC:-0.00 ) 141.47 0 0.00 0 0.00 0 - 90 ) 80 0 79 0 0 0 NUMBER OF TEST SPECIMEN CAST:6 0 0 0 0 204727 - 204732 0 0 0 0 0 0 1: CONCRETE SUPPLIER:CONCRETE TEST CYLINDER COMPRESSIVE RESULTS PER: ASTM: C39 P.S.I. @ 28 DAYS :UNLESS OTHERWISE NOTED ALL CYLINDERS RECEIVED: CEMENT:LBS.CYLINDER TEST UNIT CEMENT:LBS. NUMBER DATE P.S.I. GAL. COARSE AGGREGATE #1: LBS.204727 11/30/20 7 3820 X COARSE AGGREGATE #2: LBS.204728 11/30/20 7 3970 X COARSE AGGREGATE #3: LBS.204729 12/21/20 28 5250 0 FINE AGGREGATE: LBS.204730 12/21/20 28 5350 0 ADMIXTURE #1: OZS.204731 12/21/20 28 5200 0 ADMIXTURE #2: OZS.204732 01/00/00 SPARE 0 X ADMIXTURE #3: OZS. AIR ENTRAINING AGENT: OZS.0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X REPORT DISTRIBUTION:0 0 0 0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X 0 0 0 01/00/00 0 0 X RESPECTFULLY SUBMITTED,0 0 0 0 01/00/00 0 0 X CONSTRUCTION TECHNOLOGY 0 0 0 0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X ROBERT BEHAN (NICET)0 0 0 0 01/00/00 0 0 X MANAGER TECHNICAL SVCS.0 0 0 0 01/00/00 0 0 X Robert BehanRobert BehanRobert BehanRobert Behan APPLIED LOAD 2 11/23/20 100.202 204727 40's: PARTLY CLOUDY PROJECT: CONSTRUCTION TECHNOLOGY MR. CHARLES ALBRECHT R & P QUAKER II REALTY, LLC 728 QUAKER ROAD QUEENSBURY, NEW YORK 12804 NEMER CHRYSLER JEEP DODGE RAM: QUEENSBURY, NEW YORK CONCRETE TEMP. (F) (SPEC: SLUMP OF CONCRETE INTO PUMP: TIME PLACEMENT BEGAN / ENDED: CONCRETE AGE ( HOURS ) (SPEC: SLUMP ON ARRIVAL (INCHES): IF APPLICABLE: DELIVERED LOAD NUMBER: TRUCK NUMBER / TICKET NUMBER: YARDAGE DELIVERED / SUBTOTAL: LAB CYLINDER CONTROL NUMBERS: WATER: 0 0 DESIGN STRENGTH & FORMULA: 3: TIME CONC. BATCHED / ARRIVED: 47,950 DAYS UNLESS NOTED ALL TESTING IAW: ASTM: C31, C138, C143, C172, C173, C231, C470, C567, C617, C1064 DISCREPANCIES & REMARKS: 0.0 4: 0.0 5: 6: 7: 8: 1: FILE 2: SUPPLIER 49,900 0 0 65,900 65,350 0 0 0 67,200 0 0 0 0 0 0 0 0.0 0 0 0 0 JOINTA-GALUSHA CONCRETE, INC. 0 ULTIMATE 11/24/20 0.00 C O N C R E T E F I E L D I N S P E C T I O N & C O M P R E S S I O N T E S T R E S U L T S 0.00 TEST AGE 4500 FOUNDATION WALL: SOUTH WALL AND WEST WALL, SOUTH HALF FOUNDATION WALL: NORTH WALL AND WEST WALL, NORTH HALF PLACEMENT LOCATION OF LOAD # 0 0.00 45 PROPER HOT OR COLD WEATHER CURING PROTECTION FOR AMBIENT CONDITIONS IS AVAILABLE ONSITE. PER DRAWING: S-202, DETAIL: 5 GENERAL CONSTRUCTION PRACTICE: CONCRETE PROPERLY CONSOLIDATED. NO VISUAL EVIDENCE OF SEGREGATION OR COLD JOINTS. PLACEMENT AREA REINFORCEMENT: PLACEMENT AREA FORMWORK: ACCEPTABLE FOR ALIGNMENT & CLEANLINESS. FREE OF DEBRIS & STANDING WATER/ICE/SNOW. CLEANLINESS & COVER ACCEPTABLE. PROPERLY SIZED & LOCATED. PLACEMENT WEATHER PROTECTION: 4 William Street, Ballston Lake, New York 12019 Phone: (518) 399-1848 Email: constructiontech@live.com CLIENT: REPORT NUMBER: : PAGE #: 1 INSPECTION DATE: OUR FILE NUMBER:5 INSPECTOR & TEST SET: DAVE CASAW #5 ATT'N: AMBIENT WEATHER: OUR FILE LOCATION: 1 : PLACEMENT LOCATION OF LOAD # 2 : 0 0 0 1 2 0 0 4905 / 843690 4911 / 843 0 0 0 11.50 / 11.50 3 11.50 / 23.00 4 0.00 0 0.00 0 2.12 / 2.31 0 ##1.56 / 2.40 0 0.00 0 0.00 0 2.42 / 3.00 # 2 3.17 / 3.32 ## 0.00 0 0.00 0.00 MAX: 1.50 )2 0.80 0 1 1.60 1 0 0.00 0 0.12 5.50 3 0.56 6.00 3 0.00 0.00 0 WATER ADDED ONSITE (GALLONS):0.00 0 0.00 0 0.00 0 WATER ADDED AT DISCRETION OF:0.00 # 0.00 ##0.00 0.00 5.50 6.00 0.00 PLACEMENT SLUMP (INCH) (SPEC: - 5.00 )5.50 1 6.00 1 0.00 0 ENTRAINED AIR ( % VOL) (SPEC: - 7.00 ) 5.70 0 0.00 0 0.00 0379800 UNIT WEIGHT (PCF) (SPEC:-0.00 ) 143.85 0 0.00 0 0.00 0 - 90 ) 81 0 80 0 0 0 NUMBER OF TEST SPECIMEN CAST:6 0 0 0 0 204676 - 204681 0 0 0 0 0 0 1: CONCRETE SUPPLIER:CONCRETE TEST CYLINDER COMPRESSIVE RESULTS PER: ASTM: C39 P.S.I. @ 28 DAYS :UNLESS OTHERWISE NOTED ALL CYLINDERS RECEIVED: CEMENT:LBS.CYLINDER TEST UNIT CEMENT:LBS. NUMBER DATE P.S.I. GAL. COARSE AGGREGATE #1: LBS.204676 11/27/20 7 4010 X COARSE AGGREGATE #2: LBS.204677 11/27/20 7 3900 X COARSE AGGREGATE #3: LBS.204678 12/18/20 28 5270 0 FINE AGGREGATE: LBS.204679 12/18/20 28 5170 0 ADMIXTURE #1: OZS.204680 12/18/20 28 5400 0 ADMIXTURE #2: OZS.204681 01/00/00 SPARE 0 X ADMIXTURE #3: OZS. AIR ENTRAINING AGENT: OZS.0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X REPORT DISTRIBUTION:0 0 0 0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X 0 0 0 01/00/00 0 0 X RESPECTFULLY SUBMITTED,0 0 0 0 01/00/00 0 0 X CONSTRUCTION TECHNOLOGY 0 0 0 0 01/00/00 0 0 X 0 0 0 0 01/00/00 0 0 X ROBERT BEHAN (NICET)0 0 0 0 01/00/00 0 0 X MANAGER TECHNICAL SVCS.0 0 0 0 01/00/00 0 0 X PROPER HOT OR COLD WEATHER CURING PROTECTION FOR AMBIENT CONDITIONS IS AVAILABLE ONSITE. PER DRAWING: S-202, DETAIL: 5 GENERAL CONSTRUCTION PRACTICE: CONCRETE PROPERLY CONSOLIDATED. NO VISUAL EVIDENCE OF SEGREGATION OR COLD JOINTS. PLACEMENT AREA REINFORCEMENT: PLACEMENT AREA FORMWORK: ACCEPTABLE FOR ALIGNMENT & CLEANLINESS. FREE OF DEBRIS & STANDING WATER/ICE/SNOW. CLEANLINESS & COVER ACCEPTABLE. PROPERLY SIZED & LOCATED. PLACEMENT WEATHER PROTECTION: FOOTING: SOUTH WALL AND WEST WALL, SOUTH HALF FOOTING: NORTH WALL AND WEST WALL, NORTH HALF PLACEMENT LOCATION OF LOAD # 0 0.00 45 C O N C R E T E F I E L D I N S P E C T I O N & C O M P R E S S I O N T E S T R E S U L T S 0.00 TEST AGE 4500 0 JOINTA-GALUSHA CONCRETE, INC. CONTRACTOR NOTIFIED: LOAD 2: OVERTIME ULTIMATE 11/23/20 0.00 0 0.0 0 0 0 0 64,900 0 0 0 0 0 0 8: 1: FILE 2: SUPPLIER 48,950 0 0 66,250 67,850 0 0 DISCREPANCIES & REMARKS: 0.0 4: 0.0 5: 6: 7: 0 0 DESIGN STRENGTH & FORMULA: 3: TIME CONC. BATCHED / ARRIVED: 50,400 DAYS UNLESS NOTED ALL TESTING IAW: ASTM: C31, C138, C143, C172, C173, C231, C470, C567, C617, C1064 DELIVERED LOAD NUMBER: TRUCK NUMBER / TICKET NUMBER: YARDAGE DELIVERED / SUBTOTAL: LAB CYLINDER CONTROL NUMBERS: WATER: CONCRETE TEMP. (F) (SPEC: SLUMP OF CONCRETE INTO PUMP: TIME PLACEMENT BEGAN / ENDED: CONCRETE AGE ( HOURS ) (SPEC: SLUMP ON ARRIVAL (INCHES): IF APPLICABLE: PROJECT: CONSTRUCTION TECHNOLOGY MR. CHARLES ALBRECHT R & P QUAKER II REALTY, LLC 728 QUAKER ROAD QUEENSBURY, NEW YORK 12804 NEMER CHRYSLER JEEP DODGE RAM: QUEENSBURY, NEW YORK Robert BehanRobert BehanRobert BehanRobert Behan APPLIED LOAD 1 11/20/20 100.202 204676 50's: CLOUDY