Glen at Hiland Meadows ILU concrete test report 74 William Street, Ballston Lake, New York 12019
Phone: (518) 399-1848 Email: constructiontech@live.com
CLIENT: REPORT NUMBER: : PAGE #: 1
INSPECTION DATE:
OUR FILE NUMBER:17
INSPECTOR & TEST SET: SCOTT ROBBINS #17
ATT'N: AMBIENT WEATHER:
THE GLEN AT HILAND MEADOWS ILU/WELLNESS EXPANSION: QUEENSBURY, NY FILE LOCATION:
1 :
PLACEMENT LOCATION OF LOAD # 2 :
PLACEMENT LOCATION OF LOAD # 3 :
1 2 0 0 3
624 / 1837793 664 / 1837794 493 / 1837795
10.00 / 10.00 #10.00 / 20.00 11 10.00 / 30.00 11.08
9.24 / 10.00 0 ##9.48 / 10.25 0 10.14 / 10.43 0
8.35 / 10.25 # 10 10.30 / 10.44 ##10.46 / 11.05 11.00
MAX: 1.50 )9 1.02 0 9 0.93 0 10 0.85 0
0.24 7.00 # 0.48 7.00 10 0.14 6.00 11
WATER ADDED ONSITE (GALLONS):0.00 0 0.00 0 0.00 0
WATER ADDED AT DISCRETION OF:0.00 # 0.00 ##0.00 0.05
7.00 7.00 6.00
PLACEMENT SLUMP (INCH) (SPEC:- 7.00 ) 7.00 0 7.00 0 6.00 0
ENTRAINED AIR ( % VOL) (SPEC:- 8.00 ) 1.40 0 0.00 0 0.00 0406200
UNIT WEIGHT (PCF) (SPEC:-0.00 ) 153.85 0 0.00 0 0.00 0
- 90 ) 75 0 75 0 76 0
NUMBER OF TEST SPECIMEN CAST:6 0 0 0 0
219674 - 219679 0 0 0 0 0 0
0
CONCRETE SUPPLIER:CONCRETE TEST CYLINDER COMPRESSIVE RESULTS PER: ASTM: C39
P.S.I. @ 28 DAYS :UNLESS OTHERWISE NOTED ALL CYLINDERS RECEIVED:
CEMENT:LBS.CYLINDER TEST UNIT
CEMENT:LBS. NUMBER DATE P.S.I.
GAL.
COARSE AGGREGATE #1: LBS.219674 08/01/22 7 4480 0
COARSE AGGREGATE #2: LBS.219675 08/01/22 7 4670 0
COARSE AGGREGATE #3: LBS.219676 08/22/22 28 0 X
FINE AGGREGATE: LBS.219677 08/22/22 28 0 X
ADMIXTURE #1: OZS.219678 08/22/22 28 0 X
ADMIXTURE #2: OZS.219679 01/00/00 SPARE 0 X
ADMIXTURE #3: OZS.
AIR ENTRAINING AGENT: OZS.0 01/00/00 0 0 X
0 0 0 0 01/00/00 0 0 X
REPORT DISTRIBUTION:0 0 0 0 01/00/00 0 0 X
0 0 0 0 01/00/00 0 0 X
0 0 0 0 01/00/00 0 0 X
0 0 0 0 01/00/00 0 0 X
0 0 0 01/00/00 0 0 X
RESPECTFULLY SUBMITTED,0 0 0 0 01/00/00 0 0 X
CONSTRUCTION TECHNOLOGY 0 0 0 0 01/00/00 0 0 X
0 0 0 0 01/00/00 0 0 X
ROBERT BEHAN (NICET)0 0 0 0 01/00/00 0 0 X
MANAGER TECHNICAL SVCS.0 0 0 0 01/00/00 0 0 X
APPLIED LOAD
7
07/25/22
1075.026
219674
70's: CLOUDY
SLAB ON GRADE: EXERCISE EQUIPMENT ROOM
0.00
45
PROPER HOT OR COLD WEATHER CURING PROTECTION FOR AMBIENT CONDITIONS IS AVAILABLE ONSITE.
PER SITE VISIT OF 05/12/14.
GENERAL CONSTRUCTION PRACTICE: CONCRETE PROPERLY CONSOLIDATED. NO VISUAL EVIDENCE OF SEGREGATION OR COLD JOINTS.
PLACEMENT AREA REINFORCEMENT:
PLACEMENT AREA FORMWORK: ACCEPTABLE FOR ALIGNMENT & CLEANLINESS. FREE OF DEBRIS & STANDING WATER/ICE/SNOW.
CLEANLINESS & COVER ACCEPTABLE. PROPERLY SIZED & LOCATED.
PROJECT:
CONSTRUCTION TECHNOLOGY
MR. DAVID WENDTH
ST. PETER'S HEALTH PARTNERS
2212 BURDETT AVENUE, 2nd FLOOR
TROY, NEW YORK 12180
0
C O N C R E T E F I E L D I N S P E C T I O N & C O M P R E S S I O N T E S T R E S U L T S
TEST AGE
4000
TIME CONC. BATCHED / ARRIVED:
DELIVERED LOAD NUMBER:
TRUCK NUMBER / TICKET NUMBER:
YARDAGE DELIVERED / SUBTOTAL:
LAB CYLINDER CONTROL NUMBERS:
SLAB ON GRADE: EXERCISE ROOM
SLAB ON GRADE: CORRIDOR 109, OFFICE W110
PLACEMENT LOCATION OF LOAD #
CONCRETE TEMP. (F) (SPEC:
SLUMP OF CONCRETE INTO PUMP:
TIME PLACEMENT BEGAN / ENDED:
CONCRETE AGE ( HOURS ) (SPEC:
SLUMP ON ARRIVAL (INCHES):
IF APPLICABLE:
58,700
0
CRANESVILLE CONCRETE, INC.
CONCRETE SLUMP IS AFTER PLASTICIZER ADDITION.
ULTIMATE
07/26/22
0.00
2.00
DISCREPANCIES & REMARKS:
0.0
0
DESIGN STRENGTH & FORMULA:
UNLESS NOTED ALL TESTING IAW: ASTM: C31, C138, C143, C172, C173, C231, C470, C567, C617, C1064
WATER:
0
0
0
0
0
0
0
8:
1: FILE
2: SUPPLIER
4:
7:3:
0
05:
6:
PLACEMENT WEATHER PROTECTION:
Robert BehanRobert BehanRobert BehanRobert Behan
0
0.0
0
0
0
0
0
0
0
0
56,300
DAYS
0.0
0
4 William Street, Ballston Lake, New York 12019
Phone: (518) 399-1848 Email: constructiontech@live.com
CLIENT: REPORT NUMBER: : PAGE #: 2
INSPECTION DATE:
OUR FILE NUMBER:17
INSPECTOR & TEST SET: SCOTT ROBBINS #17
ATT'N: AMBIENT WEATHER:
THE GLEN AT HILAND MEADOWS ILU/WELLNESS EXPANSION: QUEENSBURY, NY FILE LOCATION:
4 :
0 0 0
0 0 0
4 0 0 0 0
487 / 1837796 0 0 0 0 0 0
4.50 / 34.50 # 0.00 0 0.00 0 0.00 0 0.00 0
11.18 / 11.50 0 ## 0.00 0 0.00 0 0.00 0 0.00 0
11.52 / 12.00 # 0 0.00 0 0.00 ## 0.00 0 0.00 0.00
MAX: 1.50 )11 0.70 0 0 0.00 0 0 0.00 0
0.18 5.50 # 0.00 0.00 0 0.00 0.00 0
WATER ADDED ONSITE (GALLONS):0.00 0 0.00 0 0.00 0
WATER ADDED AT DISCRETION OF:0.00 # 0.00 ##0.00 0.00
5.50 0.00 0.00
PLACEMENT SLUMP (INCH) (SPEC:- 7.00 ) 5.50 0 0.00 0 0.00 0
ENTRAINED AIR ( % VOL) (SPEC:- 8.00 )0.00 0 0.00 0 0.00 0000
UNIT WEIGHT (PCF) (SPEC:-0.00 )0.00 0 0.00 0 0.00 0
- 90 ) 80 0 0 0 0 0
NUMBER OF TEST SPECIMEN CAST:0 0 0 0 0
0 0 0 0 0 0 0 0
0
CONCRETE SUPPLIER:CONCRETE TEST CYLINDER COMPRESSIVE RESULTS PER: ASTM: C39
P.S.I. @ 28 DAYS :UNLESS OTHERWISE NOTED ALL CYLINDERS RECEIVED:
CEMENT:LBS.CYLINDER TEST UNIT
CEMENT:LBS. NUMBER DATE P.S.I.
GAL.
COARSE AGGREGATE #1: LBS.0 08/01/22 7 1990 X
COARSE AGGREGATE #2: LBS.0 08/01/22 7 2080 X
COARSE AGGREGATE #3: LBS.0 08/22/22 28 0 X
FINE AGGREGATE: LBS.0 08/22/22 28 0 X
ADMIXTURE #1: OZS.0 08/22/22 28 0 X
ADMIXTURE #2: OZS.0 01/00/00 SPARE 0 X
ADMIXTURE #3: OZS.
AIR ENTRAINING AGENT: OZS.0 01/00/00 0 0 X
0 0 0 0 01/00/00 0 0 X
REPORT DISTRIBUTION:0 0 0 0 01/00/00 0 0 X
0 0 0 0 01/00/00 0 0 X
0 0 0 0 01/00/00 0 0 X
0 0 0 0 01/00/00 0 0 X
0 0 0 01/00/00 0 0 X
RESPECTFULLY SUBMITTED,0 0 0 0 01/00/00 0 0 X
CONSTRUCTION TECHNOLOGY 0 0 0 0 01/00/00 0 0 X
0 0 0 0 01/00/00 0 0 X
ROBERT BEHAN (NICET)0 0 0 0 01/00/00 0 0 X
MANAGER TECHNICAL SVCS.0 0 0 0 01/00/00 0 0 X0
0
0
0Robert BehanRobert BehanRobert BehanRobert Behan 0
0
3:7:0
4:8:0
0
0
1: FILE 5:0
2: SUPPLIER 6:0
0
0.0 0
0.0 0
0
0
0 0
56,300
58,700
0 DAYS APPLIED LOAD
WATER:0.0
DESIGN STRENGTH & FORMULA: 4000 07/26/22
0 TEST AGE ULTIMATE
GENERAL CONSTRUCTION PRACTICE: CONCRETE PROPERLY CONSOLIDATED. NO VISUAL EVIDENCE OF SEGREGATION OR COLD JOINTS.
PLACEMENT WEATHER PROTECTION: PROPER HOT OR COLD WEATHER CURING PROTECTION FOR AMBIENT CONDITIONS IS AVAILABLE ONSITE.
UNLESS NOTED ALL TESTING IAW: ASTM: C31, C138, C143, C172, C173, C231, C470, C567, C617, C1064
CRANESVILLE CONCRETE, INC.
DISCREPANCIES & REMARKS: CONCRETE SLUMP IS AFTER PLASTICIZER ADDITION.
PLACEMENT AREA REINFORCEMENT: CLEANLINESS & COVER ACCEPTABLE. PROPERLY SIZED & LOCATED.PER SITE VISIT OF 05/12/14.
PLACEMENT AREA FORMWORK: ACCEPTABLE FOR ALIGNMENT & CLEANLINESS. FREE OF DEBRIS & STANDING WATER/ICE/SNOW.
0.00
CONCRETE TEMP. (F) (SPEC:45
LAB CYLINDER CONTROL NUMBERS:
SLUMP OF CONCRETE INTO PUMP: IF APPLICABLE:
2.00
0.00
TIME CONC. BATCHED / ARRIVED:
TIME PLACEMENT BEGAN / ENDED:
CONCRETE AGE ( HOURS ) (SPEC:
SLUMP ON ARRIVAL (INCHES):
0
0
DELIVERED LOAD NUMBER:
TRUCK NUMBER / TICKET NUMBER:
YARDAGE DELIVERED / SUBTOTAL:
MR. DAVID WENDTH 70's: CLOUDY
PROJECT:0
C O N C R E T E F I E L D I N S P E C T I O N & C O M P R E S S I O N T E S T R E S U L T S
PLACEMENT LOCATION OF LOAD # SLAB ON GRADE: POOL STORAGE ROOM
2212 BURDETT AVENUE, 2nd FLOOR 07/25/22
TROY, NEW YORK 12180 1075.026
0
CONSTRUCTION TECHNOLOGY
ST. PETER'S HEALTH PARTNERS 7