Loading...
Blower Door Testing - preliminary SUSTAINABLE COMFORT Preliminary Blower Door Testing Site Testing Report Memory Care Project Information: ILLI/Wellness Center 39 Longview Drive Queensbury, NY 12804 Testing Parameters Memory Care Apartments: 0.3 CFM/sf @ 50 Pa Common Area: 0.4 CFM/sf @ 75 Pa General Notes: Sustainable Comfort will conduct infiltration testing on site at the Memory Care Building. The apartment units will be tested following the RESNET sampling protocol which requires seven consecutive passing tests,then allows one out of every seven units to be tested. At minimum one unit from each unit type shall be tested and the dwelling units selected for testing must be appropriately"representative" of the dwelling units in the building and demonstrate a similar distribution of unit types, level, exposure,and orientation. Proposed Sampling plan will not be disclosed to site team prior to testing. See Table 2: Sampling and Testing Table below. . Table 1: Unit Types Enclosure Blower Door UnitType Unit Modeled*Bedrooms *Bathrooms Area Area Volume Model Type Target Target CFM 1Br1stlrit 108 1 1 319.2 1295.3 2872R Multifamily 0.3CFM50/SF 388.59 18rlstEnd 164 1 1 3q5.951 14q5.31 3113.E 1 Multifamily 10.3CFM50/SF 1 433.59 Common Area 'Common 1, 0 1 0 -1102ql 299711 1q3603I I custom 1 11989 Submitted By: Nick Hinman, Sustainable Comfort, Inc. INSPECTION REPORT 1 SUSTAINABLE COMFORT Table 2: Sampling and Testing Table UNIT MODEL SET UNIT INFILTRATION SAMPLE SET 1Br1stlnt 108 388 MEMD009 1Br1stlnt 109 388 MEM0009 1Br1stlnt 110 388 MEM0003 1Br1stlnt ill 388 MEM0003 113rlstEnd 119 y33 MEM0003 18ristEnd 115 y33 MEM0003 113rlstEnd 116 433 MEMD003 iBrlstEnd 117 y33 MEMD003 113rlstEnd 120 y33 MEM0003 113rlstEnd 121 1433 MEM0002 113rlstEnd 122 L133 MEM0002 113rlstEnd 123 Q3 MEM0002 113r1stlnt 127 388 MEM0002 113r1stlnt 128 38B MEM0002 113r1stlnt 129 388 MEM0002 1Br1stlnt 155 388 MEM0002 1Br1stlnt 156 388 MEM0001 113r1stlnt 157 388 MEM0001 113r1stlnt 158 388 MEM0001 1Br1stEnd 161 433 MEM0001 1Br1stEnd 162 4133 MEM0001 113rlstEnd 163 4133 MEM0001 113rlstEnd 169 4133 MEM0001 1BrlstEnd 167 933 MEM0000 113rlstEnd 168 Q3 MEMOOOD 1BrlstEnd 169 Q3 MEMOOOO 1BrlstEnd 170 Q3 MEMOOOO 1Br1stlnt 174 388 MEMOOOO 1Br1stlnt 175 388 MEM0000 1Br1stlnt 176 388 MEMOOOO #N/A Common Area Common 11,989 MRYCMN INSPECTION REPORT 2