THE GLEN AT HILAND MEADOWS Start up ChecklistEPG Start Up Checklist
Name Date First Visit
Street 10/17/2022
City Hours
Electrical Contrator 1
Standby Prime Peakshave CO-Gen
xxxx
EngineModel C7.1 Serial Number G5A12245
Serial Number 45503923 Arrangement 456-8090
Arrangement 4694413 Rating 175 KW
Engine HP rating NA Voltage 208/120
Fuel Type DIESEL Amperage 607 A
Make ASCO Make ASCO
Model 4000 SERIES Model 4000 SERIES
Ser#2423239-001RE Ser#2423240-001RE
Voltage 208 V Voltage 208 V
Amp rating 260 AMPS Amp rating 600 AMPS
Housed Outside X Inside Building
Housing Manufacturer CAT Location in Building
Housing Serial Number N/A
Customer Data/Contractor Data
Type of Installation
Engine Data Generator Data LC5014F
THE GLEN AT HILAND MEADOWS
39 LONGVIEW DR
QUEENSBURY, NY 12804
Environment
A.E. ROSEN
ATS 1 ATS 2
Page 1 of 6 Approved KLF June 2, 2004
Mounting Adjust isolators N/A
Secured to level surface X Proper Clearances X
Lube System Fuel System Diesel
Oil level X Flexible lines X
Oil leaks X Fuel solenoid wired N/A
Cooling System Day Tank
Coolant level(JW)X Wired to emergency source N/A
Coolant level(SCAC)X Proper elevation X
Proper Ventilation X Floats operational X
Remote Radiator(if equip)N/A Alarms wired and operate X
Isolation Valves at engine N/A Return line one size larger than
supply X
Fans and pumps wired to
emergency source and
operational
N/A Day tank solenoid wired to open
only when pump runs N/A
Elevation above engine
within acceptable limits N/A
Check for leaks N/A Fuel System Gas N/A
Proper pipe sizing N/A Manual Shutoff N/A
Solenoid installed/wired N/A
Exhaust System Flex Connector (Approved)N/A
Flexes X
Condensate trap X
Muffler X
Correct Sizing X
Thimble through walls N/A
Measure/Record Gas Pressure after
solenoid valve
Proper initial fuel mixture
adjustments N/A
N/A
Pre Start Checks
Page 2 of 6 Approved KLF June 2, 2004
Batteries 115-2422 Generator
Proper size YES Voltage 208 V
Voltage 12VDC Wiring complete X
Proper battery rack YES GROUNDED Y/N Y
Charger wired X Where is it grounded X
Charger proper voltage X ATS
Float voltage setting 13.8 VDC Correct Voltage X
Equalize setting X AC connections X
Jacket Water Heater 392-0478 Open/Closed Transition
Voltage 120 V Utility
KW 1800 WATT Pick up 90%
Wired to Normal Source X Drop out 85%
Emergency
CIM/CCM Pick up 90%
Customer connection N/A Drop out 75%
Proper wire size and type N/A Time Delays
Operational N/A Start 3 SECONDS
Remote Annuciators X Transfer 0 SECONDS
Customer connection X Neutral NA
Proper wire size and type X Retransfer 10 MINUTES
Operational TESTED Cooldown 5 MINUTES
Remote Start Wiring Exerciser Set Day/Time WEDNESDAY 7:00 AM
Wired to ATSs X 20 MINUTES NO LOAD
Proper wire size and type X
Pre Start Checks
Page 3 of 6 Approved KLF June 2, 2004
Record Actual Load Bank Test Y/N NO
Oil pressure 77 PSI Operation with Load YES
Coolant Temp 175'F Frequency 60 HZ
Coolant Level OK AC Voltage
Noise and Vibration/OK OK A 208 V
Battery Charge Rate 14.1 VDC B 208 V
AC Voltage 208 V C 208 V
Frequency 60HZ N 120 V
Phase Rotation CLOCKWISE
Shutdowns (verify) Record settings AC Amperage NO BUILDING
Oil pressure X A LOAD
Coolant Temp X B
Overspeed Safety X C
Overcrank X N
Alarms (verify)
Oil pressure X ATS
Coolant Temp X Time Delay Start 3 SECONDS
Coolant Level X Time Delay Transfer 9 SECONDS TOTAL
Not in Auto X Time Delay Neutral NA
Low Battery Voltage X Time Delay Retransfer 10 MINUTES
High Battery Voltage X Cooldown 5 MINUTES
Charger Failure X
Low fuel X
High Fuel X
Critical High Fuel NA
Rupture Basin X
Low Gas PSI NA
Operational Checks (engine running)
Page 4 of 6 Approved KLF June 2, 2004
A
B
C
D
E
Checking Coolant X
Checking Oil X
Walk around inspection X
Safe starting and stopping X
Maintenance Intervals X
Weekly X
Monthly X
NONE
Final Review With Customer or Contractor
Final Installation Recommendations
Page 5 of 6 Approved KLF June 2, 2004
ED THOMPSON
Performed By Customer/Contractor
10/17/2022
Engineer Date
Signatures
Page 6 of 6 Approved KLF June 2, 2004
Date: Customer# OF CABLE USED:Location# FEET CABLE RUNSerial # Emergency Generator packageLOCATION OF GENSETALT. CHARGE RATE 5-15 MIN 1: 4.1 AMPS 2: 2.8 AMPS 3: 2.7 AMPS IDLE FROM 0-15 MINVOLTAGE AMPS POWER D.C. OIL FUEL FUEL J.W. CHARGE EXH. SAFETY CHECKLIST TRIPTIME KW PH 1 PH 2 PH 3 PH 1 PH 2 PH 3 HZ. FACTOR VOLTAGE PRESS. PRESS. CONS.TEMP. RATE TEMP. POINT OK15 45.00 208.00 208.00 208.00 125 125 125 60.00 1.00 14.10 71.00 OK 1.70 172.002.6 AMP OKSHUTDOWNS:x30 88.00 208.00 208.00 208.00 244 244 244 60.00 1.00 14.00 66.00 OK 4.30 174.002.7 AMP OKLOW OIL PRESSUREx45 133.00 208.00 208.00 208.00 369 369 369 60.00 1.00 14.00 63.00 OK 6.80 176.002.6 AMP OKHIGH COOLANT TEMP.x1 133 -> 175 208.00 208.00 208.00 369 369 369 60.00 1.00 14.00 62.00 OK 9.30178.002.6 AMP OKOVERSPEEDx1.25 175.00 208.00 208.00 208.00 486 486 486 60.00 1.00 14.00 61.00 OK 13.70178.002.6 AMP OKOVERCRANKx1.5 175.00 208.00 208.00 208.00 486 486 486 60.00 1.00 14.00 60.00 OK 13.70 178.002.6 AMP OKALARMS:1.75 175.00 208.00 208.00 208.00 486 486 486 60.00 1.00 14.00 60.00 OK 13.70180.002.6 AMP OKLOW OIL PRESSUREx2 175.00 208.00 208.00 208.00 486 486 486 60.00 1.00 14.00 60.00 OK 13.70 180.002.6 AMP OKHIGH COOLANT TEMP.x2.25 175.00 208.00 208.00 208.00 486 486 486 60.00 1.00 14.00 60.00 OK 13.70180.002.6 AMP OKLOW COOLANT TEMP.x2.5 175.00 208.00 208.00 208.00 486 486 486 60.00 1.00 14.10 60.00 OK 13.70 180.002.6 AMP OKNOT IN AUTOx2.75 175.00 208.00 208.00 208.00 486 486 486 60.00 1.00 14.00 60.00 OK 13.70180.002.6 AMP OKLOW BATTERY VOLTAGEx3 175.00 208.00 208.00 208.00 486 486 486 60.00 1.00 14.00 60.00 OK 13.70 180.002.6 AMP OKBATT CHARGER FAILUREx3.25 175.00 208.00 208.00 208.00 486 486 486 60.00 1.00 14.00 60.00 OK 13.70180.002.6 AMP OKLOW FUEL LEVEL x3.5 175.00 208.00 208.00 208.00 486 486 486 60.00 1.00 14.00 60.00 OK 13.70 180.002.6 AMP OK3.75 175.00 208.00 208.00 208.00 486 486 486 60.00 1.00 14.00 60.00 OK 13.70180.002.7 AMP OKOFF PANEL ALARMS:4 175.00 208.00 208.00 208.00 486 486 486 60.00 1.00 14.00 60.00 OK 13.70 180.002.6 AMP OKCRITICAL LOW FUEL LEVEL x4.25 175.00 208.00 208.00 208.00 486 486 486 60.00 1.00 14.00 60.00 OK 13.70180.002.6 AMP OKHIGH FUEL LEVEL x4.5 175.00 208.00 208.00 208.00 486 486 486 60.00 1.00 14.00 60.00 OK 13.70 180.002.6 AMP OKCRIT. HIGH FUEL LEVEL x4.75 175.00 208.00 208.00 208.00 486 486 486 60.00 1.00 14.10 60.00 OK 13.70180.002.6 AMP OKOVERFL. RETURN PUMP 1 x5 175.00 208.00 208.00 208.00 486 486 486 60.00 1.00 14.00 60.00 OK 13.70 180.002.6 AMP OKOVERFL. RETURN PUMP 2 x5.25 0.00 1.00 1.00 1.00 0 0 0 1.00 GPH 5.5 0.00 1.00 1.00 1.00 0 0 0 1.00ENGINE CYCLE CRANK:5.75 0.00 1.00 1.00 1.00 0 0 0 1.00SECONDS CRANKING x6 0.00 1.00 1.00 1.00 0 0 0 1.00SECONDS REST x6.25 0.00 1.00 1.00 1.00 0 0 0 1.00TOTAL CRANK CYCLES x6.5 0.00 1.00 1.00 1.00 0 0 0 1.00TOTAL CRANK SECONDS x6.75 0.00 1.00 1.00 1.00 0 0 0 1.007 0.00 1.00 1.00 1.00 0 0 0 1.00VOLTAGE REGULATOR LOW HIGH7.25 0.00 1.00 1.00 1.00 0 0 0 1.00ADJUSTMENT RANGE 95% 105%Technician Name 8036 NANEUTRAL / GROUND AMPERAGE READINGS STAYED BELOW 1 AMP DURING ALL READINGSSITE EVALUATION TECHNICIANS COMMENTSThe Glen - Engine Startup10.27.22Revison Date: 12/19/17825QUEENSBURY NY5 HOUR OVERALL TESTIDLE, 25%, 50%, 75%, 100% TESTHAWG30102139 Longview Dr., Queensbury, NY, 12804Customer WitnessLogger s/n Document No: DOC-LOADBANKTESTRESULTS Rev.0