2022.11.29_Code Testing INSPECTION REPORT 1 Code Testing Summary NYS ECCC 2020 ILU: Queensbury, NY 12804 Testing Entity Sustainable Comfort, Inc. 639 N. Salina St. Syracuse, NY 13208 Project Information: ILU 39 Longview Drive Queensbury, NY 12804 Testing Summary Inspector: Benjamin Kruse Rating Field Inspector ID Number: 8H583F Inspection Date: November 28th & 29th, 2022 Site Conditions: Temperature: 40°F Time: 9:00 a.m. – 2:00 p.m. Compliance Path: The energy rating index (ERI) approach in Section R406. Testing Methodology Apartment Air Leakage Testing: R402.4.1.3: • Testing has been conducted in accordance with Section R402.4.1.3 of the 2020 New York Energy Code. The testing target is 0.3 CFM50/sf of enclosure surface area. The calculations of the enclosure area follow the definitions in the code which include the sum of all of the exterior wall area, interior wall area, ceiling area, and floor area of each apartment unit. Testing Results: Apartment Air Leakage • Testing was conducted in accordance with ASTM E779 at 50 Pascals which resulted in a final CFM50 for each apartment. The CFM50 is then converted into CFM50/sf of enclosure area to demonstrate each unit falls below the 0.3 CFM50/sf target. Table 1 shows all the individual unit testing results with official reports below. INSPECTION REPORT 2 Table 1: Testing Results: Apartment Air Leakage RFI Certification Official RFI Certification shown from the RESNET Registry linked below: https://www1.resnet.us/registry/raters.aspx Submitted By: Benjamin Kruse, Sustainable Comfort, Inc. Rating Field Inspector ID Number: 8H583F UNIT UNIT INFILTRATION TESTING DATE UNIT INFILTRATION (CFM50) A-106 1,023 22/11/28 897 A-113 1,290 22/11/28 910 A-150 974 22/11/29 914 A-151 974 22/11/29 825 A-152 1,290 22/11/28 899 A-209 1,023 22/11/28 774 A-249 1,290 22/11/28 955 A-250 974 22/11/28 937 A-251 974 22/11/28 862 A-252 1,290 22/11/28 963 INSPECTION REPORT 3 Pictures: Exterior of Building Interior of Building All Penetrations Well Sealed All Penetrations Well Sealed Unit Blower Door Reports: Testing Company: Name:Sustainable Comfort, Inc. Address:55 Linden St, Worcester, MA 01609 Phone: 508-713-9683 greenrater.com Technician: Name:Ben Kruse Credentials:RFI # 8H583F Email:ben@greenrater.com Building Information: Project ID:ILU Address:39 Longview Drive Queensburry, NY 12804 Geo-Tag Data:Latitude: Longitude: Timestamp: Customer Information: Name:Sano-Rubin Construction Services Address:624 Delaware Ave Albany, NY 12209 Phone: 518-462-6471 Measured Leakage:0.26 CFM50/ft² (Env. Area) Leakage Target:0.30 CFM50/ft² (Env. Area) Compliance with Leakage Target:Pass Test ID:Unit 106 Purpose of Test:RESNET Multi-Pt Env. Leakage Measured CFM50:896.2 (+/- 6.8%)Effective Leakage Area: 50.0 in² Building Volume:9,223.8 ft³Enclosure Surface Area: 3,411.1 ft² Coefficient (C):72.3 (+/- 31.9%)Exponent (n): 0.644 (+/- 0.092) Correlation Coefficient:0.99699 Test Standard:RESNET 380 Multi-Point Test Mode: Depressurize Test Characteristics:Indoor Temp: 70 °F Altitude: 328.0 ft Outdoor Temp: 44 °F Time Average Period: 10 seconds Test Date and Time:2022-11-28 11:38:47 Envelope Leakage Test Test Readings: Target (Pa)Bldg (Pa)Adj Bldg (Pa)Fan (Pa)Flow (cfm)Config Baseline -0.2 -60.0 -60.9 -60.6 -30.9 1,011.8 Ring A -48.0 -42.0 -41.8 -210.4 859.0 Ring B -35.0 -36.7 -36.5 -171.0 775.2 Ring B -23.0 -24.2 -23.9 -98.2 588.8 Ring B -10.0 -12.2 -12.0 -37.2 363.9 Ring B Test Equipment: Flow Device:Model 3 110V Fan Pressure Gauge:DG1000 Serial #: 3029 Calibration Date: 2019-01-28 Deviations from Standard: None Comments: None Envelope Leakage Test Page 2 of 2Report by TEC Auto Test 1.8.0 (210), © 2021 The Energy Conservatory, Inc. Testing Company: Name:Sustainable Comfort, Inc. Address:55 Linden St, Worcester, MA 01609 Phone: 508-713-9683 greenrater.com Technician: Name:Ben Kruse Credentials:RFI # 8H583F Email:ben@greenrater.com Building Information: Project ID:ILU Address:39 Longview Drive Queensburry, NY 12804 Geo-Tag Data:Latitude: Longitude: Timestamp: Customer Information: Name:Sano-Rubin Construction Services Address:624 Delaware Ave Albany, NY 12209 Phone: 518-462-6471 Measured Leakage:0.21 CFM50/ft² (Env. Area) Leakage Target:0.30 CFM50/ft² (Env. Area) Compliance with Leakage Target:Pass Test ID:Unit 113 Purpose of Test:RESNET Multi-Pt Env. Leakage Measured CFM50:909.2 (+/- 5.5%)Effective Leakage Area: 48.3 in² Building Volume:12,176.4 ft³Enclosure Surface Area: 4,301.6 ft² Coefficient (C):67.9 (+/- 25.1%)Exponent (n): 0.663 (+/- 0.072) Correlation Coefficient:0.99826 Test Standard:RESNET 380 Multi-Point Test Mode: Depressurize Test Characteristics:Indoor Temp: 70 °F Altitude: 328.0 ft Outdoor Temp: 44 °F Time Average Period: 10 seconds Test Date and Time:2022-11-28 11:21:12 Envelope Leakage Test Test Readings: Target (Pa)Bldg (Pa)Adj Bldg (Pa)Fan (Pa)Flow (cfm)Config Baseline 0.2 -60.0 -64.0 -64.2 -36.4 1,097.3 Ring A -48.0 -47.7 -47.9 -24.9 912.0 Ring A -35.0 -33.7 -33.9 -165.2 762.1 Ring B -23.0 -23.3 -23.5 -96.5 583.8 Ring B -10.0 -11.4 -11.7 -35.2 354.1 Ring B Test Equipment: Flow Device:Model 3 110V Fan Pressure Gauge:DG1000 Serial #: 3029 Calibration Date: 2019-01-28 Deviations from Standard: None Comments: None Envelope Leakage Test Page 2 of 2Report by TEC Auto Test 1.8.0 (210), © 2021 The Energy Conservatory, Inc. Testing Company: Name:Sustainable Comfort, Inc. Address:55 Linden St, Worcester, MA 01609 Phone: 508-713-9683 greenrater.com Technician: Name:Ben Kruse Credentials:RFI # 8H583F Email:ben@greenrater.com Building Information: Project ID:ILU Address:39 Longview Drive Queensburry, NY 12804 Geo-Tag Data:Latitude: Longitude: Timestamp: Customer Information: Name:Sano-Rubin Construction Services Address:624 Delaware Ave Albany, NY 12209 Phone: 518-462-6471 Measured Leakage:0.28 CFM50/ft² (Env. Area) Leakage Target:0.30 CFM50/ft² (Env. Area) Compliance with Leakage Target:Pass Test ID:Unit 150 Purpose of Test:RESNET Multi-Pt Env. Leakage Measured CFM50:913.6 (+/- 3.9%)Effective Leakage Area: 52.4 in² Building Volume:8,623.1 ft³Enclosure Surface Area: 3,247.6 ft² Coefficient (C):76.7 (+/- 17.7%)Exponent (n): 0.633 (+/- 0.051) Correlation Coefficient:0.99904 Test Standard:RESNET 380 Multi-Point Test Mode: Depressurize Test Characteristics:Indoor Temp: 70 °F Altitude: 328.0 ft Outdoor Temp: 40 °F Time Average Period: 10 seconds Test Date and Time:2022-11-29 09:21:10 Envelope Leakage Test Test Readings: Target (Pa)Bldg (Pa)Adj Bldg (Pa)Fan (Pa)Flow (cfm)Config Baseline -0.3 -60.0 -60.4 -60.1 -33.4 1,051.0 Ring A -48.0 -49.9 -49.5 -27.3 952.6 Ring A -35.0 -35.8 -35.5 -176.2 786.8 Ring B -23.0 -24.0 -23.7 -103.8 605.2 Ring B -10.0 -11.4 -11.1 -36.9 362.8 Ring B Test Equipment: Flow Device:Model 3 110V Fan Pressure Gauge:DG1000 Serial #: 3029 Calibration Date: 2019-01-28 Deviations from Standard: None Comments: None Envelope Leakage Test Page 2 of 2Report by TEC Auto Test 1.8.0 (210), © 2021 The Energy Conservatory, Inc. Testing Company: Name:Sustainable Comfort, Inc. Address:55 Linden St, Worcester, MA 01609 Phone: 508-713-9683 greenrater.com Technician: Name:Ben Kruse Credentials:RFI # 8H583F Email:ben@greenrater.com Building Information: Project ID:ILU Address:39 Longview Drive Queensburry, NY 12804 Geo-Tag Data:Latitude: Longitude: Timestamp: Customer Information: Name:Sano-Rubin Construction Services Address:624 Delaware Ave Albany, NY 12209 Phone: 518-462-6471 Measured Leakage:0.25 CFM50/ft² (Env. Area) Leakage Target:0.30 CFM50/ft² (Env. Area) Compliance with Leakage Target:Pass Test ID:Unit 151 Purpose of Test:RESNET Multi-Pt Env. Leakage Measured CFM50:824.1 (+/- 3.3%)Effective Leakage Area: 45.7 in² Building Volume:8,623.1 ft³Enclosure Surface Area: 3,247.6 ft² Coefficient (C):65.7 (+/- 14.9%)Exponent (n): 0.647 (+/- 0.043) Correlation Coefficient:0.99935 Test Standard:RESNET 380 Multi-Point Test Mode: Depressurize Test Characteristics:Indoor Temp: 70 °F Altitude: 328.0 ft Outdoor Temp: 40 °F Time Average Period: 10 seconds Test Date and Time:2022-11-29 09:38:18 Envelope Leakage Test Test Readings: Target (Pa)Bldg (Pa)Adj Bldg (Pa)Fan (Pa)Flow (cfm)Config Baseline -0.1 -60.0 -60.2 -60.1 -27.4 954.9 Ring A -48.0 -47.1 -47.0 -198.4 834.3 Ring B -35.0 -35.2 -35.1 -138.0 696.9 Ring B -23.0 -23.4 -23.3 -80.8 534.6 Ring B -10.0 -11.6 -11.5 -30.4 329.6 Ring B Test Equipment: Flow Device:Model 3 110V Fan Pressure Gauge:DG1000 Serial #: 3029 Calibration Date: 2019-01-28 Deviations from Standard: None Comments: None Envelope Leakage Test Page 2 of 2Report by TEC Auto Test 1.8.0 (210), © 2021 The Energy Conservatory, Inc. Testing Company: Name:Sustainable Comfort, Inc. Address:55 Linden St, Worcester, MA 01609 Phone: 508-713-9683 greenrater.com Technician: Name:Ben Kruse Credentials:RFI # 8H583F Email:ben@greenrater.com Building Information: Project ID:ILU Address:39 Longview Drive Queensburry, NY 12804 Geo-Tag Data:Latitude: Longitude: Timestamp: Customer Information: Name:Sano-Rubin Construction Services Address:624 Delaware Ave Albany, NY 12209 Phone: 518-462-6471 Measured Leakage:0.21 CFM50/ft² (Env. Area) Leakage Target:0.30 CFM50/ft² (Env. Area) Compliance with Leakage Target:Pass Test ID:Unit 152 Purpose of Test:RESNET Multi-Pt Env. Leakage Measured CFM50:898.1 (+/- 0.7%)Effective Leakage Area: 46.9 in² Building Volume:12,176.4 ft³Enclosure Surface Area: 4,301.6 ft² Coefficient (C):65.3 (+/- 3.0%)Exponent (n): 0.670 (+/- 0.009) Correlation Coefficient:0.99998 Test Standard:RESNET 380 Multi-Point Test Mode: Depressurize Test Characteristics:Indoor Temp: 70 °F Altitude: 328.0 ft Outdoor Temp: 44 °F Time Average Period: 10 seconds Test Date and Time:2022-11-28 10:35:37 Envelope Leakage Test Test Readings: Target (Pa)Bldg (Pa)Adj Bldg (Pa)Fan (Pa)Flow (cfm)Config Baseline -0.4 -60.0 -59.9 -59.5 -33.5 1,053.7 Ring A -48.0 -48.7 -48.3 -25.3 917.7 Ring A -35.0 -34.9 -34.5 -153.4 734.4 Ring B -23.0 -24.2 -23.8 -91.2 567.8 Ring B -10.0 -11.9 -11.5 -34.5 350.9 Ring B Test Equipment: Flow Device:Model 3 110V Fan Pressure Gauge:DG1000 Serial #: 3029 Calibration Date: 2019-01-28 Deviations from Standard: None Comments: None Envelope Leakage Test Page 2 of 2Report by TEC Auto Test 1.8.0 (210), © 2021 The Energy Conservatory, Inc. Testing Company: Name:Sustainable Comfort, Inc. Address:55 Linden St, Worcester, MA 01609 Phone: 508-713-9683 greenrater.com Technician: Name:Ben Kruse Credentials:RFI # 8H583F Email:ben@greenrater.com Building Information: Project ID:ILU Address:39 Longview Drive Queensburry, NY 12804 Geo-Tag Data:Latitude: Longitude: Timestamp: Customer Information: Name:Sano-Rubin Construction Services Address:624 Delaware Ave Albany, NY 12209 Phone: 518-462-6471 Measured Leakage:0.23 CFM50/ft² (Env. Area) Leakage Target:0.30 CFM50/ft² (Env. Area) Compliance with Leakage Target:Pass Test ID:Unit 209 Purpose of Test:RESNET Multi-Pt Env. Leakage Measured CFM50:773.5 (+/- 4.2%)Effective Leakage Area: 48.3 in² Building Volume:9,223.8 ft³Enclosure Surface Area: 3,411.1 ft² Coefficient (C):74.2 (+/- 18.9%)Exponent (n): 0.599 (+/- 0.054) Correlation Coefficient:0.99879 Test Standard:RESNET 380 Multi-Point Test Mode: Depressurize Test Characteristics:Indoor Temp: 70 °F Altitude: 328.0 ft Outdoor Temp: 44 °F Time Average Period: 10 seconds Test Date and Time:2022-11-28 09:59:47 Envelope Leakage Test Test Readings: Target (Pa)Bldg (Pa)Adj Bldg (Pa)Fan (Pa)Flow (cfm)Config Baseline 0.3 -60.0 -58.6 -58.9 -228.1 894.1 Ring B -48.0 -48.5 -48.8 -179.4 793.9 Ring B -35.0 -34.6 -35.0 -118.7 646.9 Ring B -23.0 -23.6 -24.0 -70.3 499.1 Ring B -10.0 -10.8 -11.1 -30.8 331.5 Ring B Test Equipment: Flow Device:Model 3 110V Fan Pressure Gauge:DG1000 Serial #: 3029 Calibration Date: 2019-01-28 Deviations from Standard: None Comments: None Envelope Leakage Test Page 2 of 2Report by TEC Auto Test 1.8.0 (210), © 2021 The Energy Conservatory, Inc. Testing Company: Name:Sustainable Comfort, Inc. Address:55 Linden St, Worcester, MA 01609 Phone: 508-713-9683 greenrater.com Technician: Name:Ben Kruse Credentials:RFI # 8H583F Email:ben@greenrater.com Building Information: Project ID:ILU Address:39 Longview Drive Queensburry, NY 12804 Geo-Tag Data:Latitude: Longitude: Timestamp: Customer Information: Name:Sano-Rubin Construction Services Address:624 Delaware Ave Albany, NY 12209 Phone: 518-462-6471 Measured Leakage:0.22 CFM50/ft² (Env. Area) Leakage Target:0.30 CFM50/ft² (Env. Area) Compliance with Leakage Target:Pass Test ID:Unit 249 Purpose of Test:RESNET Multi-Pt Env. Leakage Measured CFM50:954.2 (+/- 1.7%)Effective Leakage Area: 58.7 in² Building Volume:12,176.4 ft³Enclosure Surface Area: 4,301.6 ft² Coefficient (C):89.4 (+/- 7.6%)Exponent (n): 0.605 (+/- 0.022) Correlation Coefficient:0.99980 Test Standard:RESNET 380 Multi-Point Test Mode: Depressurize Test Characteristics:Indoor Temp: 70 °F Altitude: 328.0 ft Outdoor Temp: 40 °F Time Average Period: 10 seconds Test Date and Time:2022-11-28 10:16:58 Envelope Leakage Test Test Readings: Target (Pa)Bldg (Pa)Adj Bldg (Pa)Fan (Pa)Flow (cfm)Config Baseline -2.9 -60.0 -63.7 -60.8 -37.9 1,118.3 Ring A -48.0 -51.1 -48.2 -28.1 966.0 Ring A -35.0 -36.1 -33.2 -176.0 786.4 Ring B -23.0 -26.0 -23.1 -111.4 626.9 Ring B -10.0 -14.0 -11.2 -44.8 399.2 Ring B Test Equipment: Flow Device:Model 3 110V Fan Pressure Gauge:DG1000 Serial #: 3029 Calibration Date: 2019-01-28 Deviations from Standard: None Comments: None Envelope Leakage Test Page 2 of 2Report by TEC Auto Test 1.8.0 (210), © 2021 The Energy Conservatory, Inc. Testing Company: Name:Sustainable Comfort, Inc. Address:55 Linden St, Worcester, MA 01609 Phone: 508-713-9683 greenrater.com Technician: Name:Ben Kruse Credentials:RFI # 8H583F Email:ben@greenrater.com Building Information: Project ID:ILU Address:39 Longview Drive Queensburry, NY 12804 Geo-Tag Data:Latitude: Longitude: Timestamp: Customer Information: Name:Sano-Rubin Construction Services Address:624 Delaware Ave Albany, NY 12209 Phone: 518-462-6471 Measured Leakage:0.29 CFM50/ft² (Env. Area) Leakage Target:0.30 CFM50/ft² (Env. Area) Compliance with Leakage Target:Pass Test ID:Unit 250 Purpose of Test:RESNET Multi-Pt Env. Leakage Measured CFM50:936.4 (+/- 9.7%)Effective Leakage Area: 54.2 in² Building Volume:8,623.1 ft³Enclosure Surface Area: 3,247.6 ft² Coefficient (C):79.7 (+/- 44.4%)Exponent (n): 0.630 (+/- 0.127) Correlation Coefficient:0.99399 Test Standard:RESNET 380 Multi-Point Test Mode: Depressurize Test Characteristics:Indoor Temp: 70 °F Altitude: 328.0 ft Outdoor Temp: 44 °F Time Average Period: 10 seconds Test Date and Time:2022-11-28 09:41:26 Envelope Leakage Test Test Readings: Target (Pa)Bldg (Pa)Adj Bldg (Pa)Fan (Pa)Flow (cfm)Config Baseline -0.4 -60.0 -60.0 -59.6 -37.9 1,118.2 Ring A -48.0 -48.3 -47.9 -28.5 974.2 Ring A -35.0 -36.5 -36.2 -171.6 776.6 Ring B -23.0 -25.9 -25.5 -99.9 593.8 Ring B -10.0 -11.3 -10.9 -42.4 388.6 Ring B Test Equipment: Flow Device:Model 3 110V Fan Pressure Gauge:DG1000 Serial #: 3029 Calibration Date: 2019-01-28 Deviations from Standard: None Comments: None Envelope Leakage Test Page 2 of 2Report by TEC Auto Test 1.8.0 (210), © 2021 The Energy Conservatory, Inc. Testing Company: Name:Sustainable Comfort, Inc. Address:55 Linden St, Worcester, MA 01609 Phone: 508-713-9683 greenrater.com Technician: Name:Ben Kruse Credentials:RFI # 8H583F Email:ben@greenrater.com Building Information: Project ID:ILU Address:39 Longview Drive Queensburry, NY 12804 Geo-Tag Data:Latitude: Longitude: Timestamp: Customer Information: Name:Sano-Rubin Construction Services Address:624 Delaware Ave Albany, NY 12209 Phone: 518-462-6471 Measured Leakage:0.27 CFM50/ft² (Env. Area) Leakage Target:0.30 CFM50/ft² (Env. Area) Compliance with Leakage Target:Pass Test ID:Unit 251 Purpose of Test:RESNET Multi-Pt Env. Leakage Measured CFM50:861.6 (+/- 7.9%)Effective Leakage Area: 56.6 in² Building Volume:8,623.1 ft³Enclosure Surface Area: 3,247.6 ft² Coefficient (C):89.3 (+/- 35.1%)Exponent (n): 0.579 (+/- 0.102) Correlation Coefficient:0.99548 Test Standard:RESNET 380 Multi-Point Test Mode: Depressurize Test Characteristics:Indoor Temp: 70 °F Altitude: 328.0 ft Outdoor Temp: 40 °F Time Average Period: 10 seconds Test Date and Time:2022-11-28 09:29:57 Envelope Leakage Test Test Readings: Target (Pa)Bldg (Pa)Adj Bldg (Pa)Fan (Pa)Flow (cfm)Config Baseline 0.4 -60.0 -60.7 -61.1 -31.3 1,019.0 Ring A -48.0 -46.1 -46.6 -188.7 813.9 Ring B -35.0 -32.9 -33.4 -155.6 739.7 Ring B -23.0 -23.4 -23.8 -99.3 592.1 Ring B -10.0 -10.6 -11.1 -38.2 369.0 Ring B Test Equipment: Flow Device:Model 3 110V Fan Pressure Gauge:DG1000 Serial #: 3029 Calibration Date: 2019-01-28 Deviations from Standard: None Comments: None Envelope Leakage Test Page 2 of 2Report by TEC Auto Test 1.8.0 (210), © 2021 The Energy Conservatory, Inc. Testing Company: Name:Sustainable Comfort, Inc. Address:55 Linden St, Worcester, MA 01609 Phone: 508-713-9683 greenrater.com Technician: Name:Ben Kruse Credentials:RFI # 8H583F Email:ben@greenrater.com Building Information: Project ID:ILU Address:39 Longview Drive Queensburry, NY 12804 Geo-Tag Data:Latitude: Longitude: Timestamp: Customer Information: Name:Sano-Rubin Construction Services Address:624 Delaware Ave Albany, NY 12209 Phone: 518-462-6471 Measured Leakage:0.22 CFM50/ft² (Env. Area) Leakage Target:0.30 CFM50/ft² (Env. Area) Compliance with Leakage Target:Pass Test ID:Unit 252 Purpose of Test:RESNET Multi-Pt Env. Leakage Measured CFM50:963.0 (+/- 2.0%)Effective Leakage Area: 69.1 in² Building Volume:12,176.4 ft³Enclosure Surface Area: 4,301.6 ft² Coefficient (C):114.5 (+/- 8.5%)Exponent (n): 0.544 (+/- 0.025) Correlation Coefficient:0.99970 Test Standard:RESNET 380 Multi-Point Test Mode: Depressurize Test Characteristics:Indoor Temp: 70 °F Altitude: 328.0 ft Outdoor Temp: 40 °F Time Average Period: 10 seconds Test Date and Time:2022-11-28 09:12:15 Envelope Leakage Test Test Readings: Target (Pa)Bldg (Pa)Adj Bldg (Pa)Fan (Pa)Flow (cfm)Config Baseline -1.9 -60.0 -62.4 -60.5 -36.1 1,091.7 Ring A -48.0 -48.4 -46.5 -266.9 966.4 Ring B -35.0 -37.3 -35.4 -198.6 834.9 Ring B -23.0 -25.2 -23.3 -122.6 657.5 Ring B -10.0 -11.7 -9.9 -47.4 410.5 Ring B Test Equipment: Flow Device:Model 3 110V Fan Pressure Gauge:DG1000 Serial #: 3029 Calibration Date: 2019-01-28 Deviations from Standard: None Comments: None Envelope Leakage Test Page 2 of 2Report by TEC Auto Test 1.8.0 (210), © 2021 The Energy Conservatory, Inc.