IM Inspection Worksheet_01-11-2023_08-06-13INSPECTION WORKSHEET (COMFIN-028626-2023)
CC-0061-2023Case Number:Case Module:Permit Management
11/01/2023 Partial PassInspection Status:Inspection Date:
Commercial Final InspectionInspection Type:Inspector:Mark Smith
Job Address:Parcel Number:756 Glen St
Queensbury, NY 12804
302.6-1-51.2
Company Name NameContact Type
Applicant JET Enterprises HC3 LLC
Contractor JET Enterprises TSC2 LLC
Granted Permission Dave's Hot Chicken
Primary Owner QUEENSBURY PLAZA I, LLC
Checklist Item CommentsPassed
Low flow toilet 1.3 gal/flushing cycle True
Building Inspector Notes False 10/27/23 final commercial inspection not approved. Please
address the items listed below and call for recheck when ready.
- One hour fire rated wall that separates the kitchen from storage
area will need to be repaired and fire caulking and rockwool
installed at the roof deck and at all penetrations.
- 2 hour fire rated wall at corridor leading to back door needs to be
fire caulked at open penetrations.
- Provide a certified letter of substantial completion from design
engineer stating that the project was completed in accordance
with the approve3d plans and specifications.
- Install missing ceiling tiles in kitchen ceiling.
- provide air balancing report.
-install handicapped signs at restrooms.
-provide electronic as built drawings.
-install 4" building numbers at front door.
- Complete Fire Marshall's Items.
11/1/23 partial approval for final commercial inspection.
- Approved for temporary Certificate of Occupancy only.
remaining items.
-Submit air balancing report.
-Submit electronic as built drawings
Bldg Access All Sides 20ft Drivable Surface True
H/C rear grab bar 36" with 24" to open side True
Public Toilet Room Handicapped Accessible True
Firewalls, 2 Hr, 3 Hr / Fire Dampers / Fire Doors True
Handicap parking striping True
Bldg Num or Tenant Address on Bld or Drive True
Gas Shut-off Exposed & Regulator 12" min abv grd True
Handicapped Service Counters 34 inch True
H/C side & rear grab bars 36" above floor True
HVAC air balancing report False provide air balancing report
H/C sinks 34" above floor True
H/C 18" minimum vertical grab bar True
Engineer or Architect Approval True
Hot water drain pan to indirect waste True
November 01, 2023 Page 1 of 2
INSPECTION WORKSHEET (COMFIN-028626-2023)
Checklist Item CommentsPassed
H/C grab bar: 42" side, 12" from center True
OK to Issue C/O False
Universal Symbol of Access displayed True
Final Electrical / Flex Gas Piping Bonded True
Plumbing Vent Through Roof/Roof complete True
Relief Valve ,Heat Trap/Water Temp 110 deg or less True
Electronic as-builts False provide electronic as built drawings
Handicapped Bath/Parking Lot Signage True
Exits At Grade Or Platform 36 (w) x 44 (l)True
H/C mirrors 40" above floor True
H/C toilet flush handle on open side True
OK to Issue Temporary C/O False 11/1/23 approved for temp C.O only
H/C vertical grab bar 39" from floor and corner True
Ext Finish /Grade Complete/6 in 10ft or Equivalent True
Doors 36 inch wLever Hand Panic Hardware, if req True
Attic Access 30 x 20 x 30 (h)True
Floor Bathroom Watertight Other Floors Okay True
November 01, 2023 Page 2 of 2