IM Inspection Worksheet_13-11-2023_12-35-12INSPECTION WORKSHEET (RPLUM-028855-2023)
RC-0553-2022Case Number:Case Module:Permit Management
11/13/2023 Partial PassInspection Status:Inspection Date:
Rough PlumbingInspection Type:Inspector:Charles Dyer
Job Address:Parcel Number:21 Duncan Cv
Queensbury, NY 12804
226.16-1-7
Company Name NameContact Type
Applicant AJA Architecture & Planning
Architect AJA Architecture & Planning
Contractor Hilltop Construction
Granted Permission Stephen Orban
MEGHAN ORBAN
Primary Owner Stephen Orban
MEGHAN ORBAN
Checklist Item CommentsPassed
Building Inspector Notes False Rough plumbing approved / call when ready for air sealing and
firestopping. Please call fire marshal 518-761-8206 when ready
for fireplace inspection.
Pressure Test False Verified PEX for hot & cold @ 60+ psi approved
Pressure Test True
3" Vent Through Roof - 18" min True
Washing Machine Drain 2 inch minimum True
All Return Air Hard Duct Work True Not completed at time of inspection / completed
5 psi or 10 ft. above highest conn. for 15 minutes True
Rough Plumbing / Nail Plates True
Duct Testing Outside Conditioned Space False N/A
Plumbing Under Slab True 12/7/22 for 2" SCHD 40 drain and PEX supply for wet bar only,
verified holding air (psi)
Water Supply Piping False Will need to verify pressure when copper lines are completed
Duct Insulation - if required in unheated spaces True
Duct work sealed properly False Not completed at time of inspection. 11/13/23 will need verification
sealing of duct work at crawl area.
Cleanout every 100 feet change of direction True
Plumbing Vent Vents in Place True
Air Test Gas Piping 10 psi for 10 Minutes False
Washing Machine Trap: 18"-42" discharge True
Air Head True
Air Head True
50 P.S.I for 15 minutes True PEX
1 ½ inch minimum Drain Size True
Drain Vent True
Permit Card Visible From Road True At pole
November 13, 2023 Page 1 of 1