IM Inspection Worksheet_07-12-2023_15-18-03INSPECTION WORKSHEET (RESFINAL-029211-2023)
RC-0578-2022Case Number:Case Module:Permit Management
12/07/2023 Partial PassInspection Status:Inspection Date:
Residential Final InspectionInspection Type:Inspector:Charles Dyer
Job Address:Parcel Number:42 Farr Ln
Queensbury, NY 12804
295.20-1-4.2
Company Name NameContact Type
Applicant RICHARD SPOERL
Contractor David Howard Jr
Engineer Engineering America Company
Granted Permission RICHARD SPOERL
Primary Owner RICHARD SPOERL
Checklist Item CommentsPassed
Low flow toilet 1.3 gal/flushing cycle False
Bathroom Fans, if no window True
3" Plumbing Vent through roof minimum 18 inch True
Grade away from foundation: 6" down, 10' out True
Final Survey Plot Plan False to be provided
Window guards req:<2' above floor/6' above grade True
Interior privacy/trim/doors/main entrance 36 False
Backflow Preventors where required True
Basement wall insulation R- value verified False
Emergency egress below grade True
Intake Openings False
Safety glazing: w/in 5' of tub/shower True
Seals on Garage Doors, esp. Wood True
Not less than 3' horiz from opening of bthrn True
Basement ceiling covered 2x8 fl joist or less False N/A
Attic Access Insulation = Attic R- Value True
Gas Shut-off Exposed & Regulator 12" min abv grd True
Platform at all exterior doors True
Garage Floor Pitched True
Inter Connected True
Arc Fault Breaker Habitable Spaces True
Dryer Duct Max Length 35', Labeled Over 35'False
Energy Sticker on Elec. Panel:R-Val. & Heating Sys True
Furnace/Hot Water Heater operating True hot water
Fresh Air Intake False
Chimney Rain Cap Installed True
Basement stairs closed rise greater than 4 inches False to be provided
Foam in basement/attics covered w/thermal barrier False N/A
Outside every bedroom area True
December 07, 2023 Page 1 of 3
INSPECTION WORKSHEET (RESFINAL-029211-2023)
Checklist Item CommentsPassed
Blower Door Test Certification False to be provided
Fin Elect; Energy Saving Light Bulbs 90 Percent True
Heat detector in garage True
Gas Log In Sealed or Glass Enclosure True need to verify operation for final
OK to Issue C/O False
Truss ID Signage Installed at Electrical Meter False
Range Hood 400+ cfm-Fresh Air REQUIRED False
4 inch Building Number Address visible from road False
CO in bedrooms w/gas appliances False
Attic Access Gasketed True
Jack posts in basement lagged at top and bottom True
6" clearance to sill plate True
Crawl space/knee wall access insulated & gasketed False
20 Minute Fire Door/Self-Closing Hardware True
Every level, Every bedroom True
Furnace shut-off w/in 30 ft. or w/in line of site False N/A
Chimney Height / B Vent / Direct Vent Location True
within 10' of all sleeping areas True
on all levels w/gas appliances (i.e. furnace)True
Relief Valve ,Heat Trap/Water Temp 110 deg or less True
1/2" Gypsum or House Wall and Gable True
Basement Egress: 5s.f. window w/sill or Bilco door True
Bathroom / Kitchen Watertight False
Fresh air supply 3' from grade False
Pull down stairs boxed out and insulated False
OK to Issue Temporary C/O True ok to issue temp C/O
General Comments True Walk through for list of items to be completed for Temp C/O at this
time
Conditions for Temp C/O 1. provide final survey 2.provide blower
door test results 3. complete HRV 4. complete exterior 5. provide
truss ID
Foundation insulation to floor False
Carbon Monoxide Detectors:True
Duct work sealed properly False N/A
Flex Gas Pipe Bonding True
HRV or ERV Installed per Bedroom Requirements False to be provided
Smoke Detectors:True
Battery backup True
Attic Access 22 x 30 minimum True
Roof Complete / Exterior Finish Complete True
As Built Septic System False to be provided
Outside Spigots have Air Gap True
Encl. Stairs Sheetrock Underside minimum ½ Gypsum False
Handrail 4 or more risers False provide handrail at basement stairs as discussed
December 07, 2023 Page 2 of 3
INSPECTION WORKSHEET (RESFINAL-029211-2023)
Checklist Item CommentsPassed
Guard at stairwell at 34" or more True
Interior/Exterior Railings 34 to 38 False
Handrail Termination at Newell Post or Wall False
All Hot Water Systems: 3/4" or larger piping R-3 False
Plumbing fixtures False