Loading...
ChecklistReport001-30-24 022456 INSPECTION WORKSHEET Town of Queensbury - Building and Codes - Fire Marshal 742 Bay Road - (518) 761-8256 Building (518) 761-8206 Fire Marshal Case Number: RC-0755-2023 Case Module: Permit Inspection Date: January 30, 2024 Inspection Status: Reinspect Inspector: Mark Smith Inspection Type: Rough Plumbing Job Address: , Parcel Number: Contact Type Company Name Name N/A Granted Permission N/A Primary Owner N/A Checklist Item Status Permit card visible from road PASS Building Inspector notes 1/30/24 Partial approval for rough plumbing - sanitary drains and vents only approved PASS Rough plumbing, nail plates PASS Plumbing vent, vents in place PASS 3 inches vent through roof - 18 inches minimum exposed PASS 1 1/2 inch minimum drain size PASS Washing machine drain, 2 inches minimum PASS Washing machine trap: 18 inches-42 inches discharge PASS Cleanout every 100 feet change of direction PASS Drain and venting PASS Pressure test FAIL Air or head test PASS 5 psi or 10 ft. above highest connection for 15 minutes PASS Water supply piping FAIL Water supply piping pressure test FAIL Water supply piping air or head test FAIL 50 psi for 15 minutes FAIL Air test gas piping 10 psi for 10 minutes FAIL All return air duct work must be hard piped FAIL Duct insulation- if required in unheated spaces FAIL Duct Blaster Test for duct work, minimum R-8, unheated spaces FAIL Duct work sealed properly FAIL Mark Smith Code Enforcement Officer